ABB i-bus KNXStart-upJRA/S | 2CDC 506 051 D0204 973.3.2 Communication objects GeneralThese communication objects are only available once per device for all operation modes and serve theinterdisciplinary functions.No. Function Object name Data type Flags0 In operation General 1 bitDPT 1.002C, R, TThe communication object is enabled if the parameter Send communication object "In operation" in the General parameterwindow was selected as Yes.In order to monitor the operation of the blind/roller shutter actuator at regular intervals, an In operation telegram can be sentcyclically to the bus.As long as the communication object is activated, it sends a parameterizable In operation telegram.1 Request status values General 1 bitDPT 1.017C, WIf a telegram with the value x (x = 0/1/0 or 1) is received at this communication object, all the status objects are sent to thebus, as long as they were not programmed with the option On change or request.Option x = 1 produces the following function:Telegram value: 1 = All status messages, provided they are programmed with the option On change or request,are sent.0 = No reaction.2 Disable/enable man. operation General 1 bitDPT 1.003C, WUsing this communication object, Manual operation is disabled or enabled.Using the value 0, the button is enabled on the device.Using the value 1, the button is disabled on the device.Telegram value: 0 = Button enabled1 = Button disabled3 Status Man. operation General 1-byteDPT 1.011C, R, TThis communication object indicates whether manual operation is activated.Telegram value: 0 = Manual operation not active1 = Manual operation activeThe status of manual operation is sent, depending on parameterization, On change, On request and On change or request.