SM01P 1811 SCL/SCM CONTROL WIRING DIAGRAMS11.1 SCL/SCM Terminal StripShown below is the control terminal strip, along with a brief description of the function ofeach terminal The following wiring diagram examples provide a quick reference to wirethe drive for the most common configurationsMaintainedRUN/STOPContact1 2 2513A 13E13BRUN5 6 11 16 17SIGNAL COMMON0-10V DC INPUTTB-13A FUNCTION SELECTTB-13B FUNCTION SELECTTB-13E FUNCTION SELECT4-20mA INPUTFORM A RELAY- + +SPEED POT POWER SUPPLYDIGITAL INPUT REFERENCESCL/SCM Terminal StripNOTE• The function of terminals TB-13A, 13B, 13E and the Form A relay at terminals16 and 17 are dependent on the programming of certain parametersRefer to Section 15, DESCRIPTION OF PARAMETERS• The digital inputs (terminals 1, 13A, 13B, and 13E) are active-high They canbe activated using terminal 11 (which is +12 VDC) as shown in the followingdiagrams, or by using an external voltage source with a range of +12 VDC to+28 VDC (+ 10%)Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com