23Please keep plastic packaging bags away from babies andchildren in order to safeguard against suffocation accidents.Handle the components with care. Please take into account theweight. It may be necessary to engage the help of a secondperson.4.2 Transport to Installation SiteThe PROTECT 1. is equipped with transport rolls for easytransport to the intended installation site. It is recommended toinstall the UPS where:♦ The connection work can be conveniently carried out;♦ There is enough space for proper operation and, ifnecessary, for periodic and extraordinary maintenancework; in this regard, the connection cables should belong enough to move the UPS (to open the UPS ifnecessary) without having to switch it off.♦ The use of an external manual bypass is recommended♦ The UPS is protected against external atmosphericinfluences;♦ The humidity and the ambient temperature are within thelimits;♦ The fire protection standards are observed.The battery service life strongly depends on the ambienttemperature. Ambient temperatures between+ 15° and + 25°Care optimum.Attention!Only transport the PROTECT 1. in an uprightposition! Never tilt or cant it; avoid displacingthe centre of gravity!Make sure that no magnetic storage media are stored and/oroperated close to PROTECT 1.4.3 Set-UpNote the following points when setting up the UPS system andits external battery units (special accessories):