69EN4.4 User settingsSubmenu Available settings Default settingsPassword Can be changed by user 4732Change language English, Italiano, Français, Deutsch,Español, Русский, Polski, 简体中文 EnglishUser password [enabled, ****], [disabled] enabledAudible alarms [enabled], [disabled] enabledOutput voltage [200V], [208V], [220V], [230V], [240V] [230V]Output frequency [autosensing], [converter 50Hz, 60Hz] autosensingHigh efficiency mode [disabled], [enabled] disabledAuto bypass [disabled], [enabled] disabledStart/Autorestart/Start frombypass[disabled], [enabled]Cold start/Autorestart: enabledStart from bypass:disabledSite wiring fault [enabled], [disabled] disabledOverload pre-alarm [10%~100%] 100%External battery [Auto detection],[Manual EBP: 0~6], Auto detectionCharger current [2A], [4A], [6A], [8A] for long backupmodel 4ADry in signal [Disabled], [Remote on], [Remote off],[Forced bypass] disabledDry out signal [load powered], [on bat], [Low bat], [batopen], [bypass], [ups ok] bypass