493.3.8 ZonesThe Commission Zones option lists all the zones in use by this panel and allows the zone text description to bechanged.[Commission Zones]Zone Location0001 BASEMENT WEST0002 RECEPTION0015 EAST WING0018 TOWER BLOCKTo change the location text assigned to the Zone, press the ✔ button when the Zone Location Text ishighlighted. Refer to Section 3.1.4 for guidance on how to change text descriptions.To select a different zone, use either the scroll up/down keys, or just type in the number of the required zone,followed by the ✔ button. Note that only zones in use are displayed.3.3.9 ExitTo exit the Commission Mode and return the panel to normal operation (i.e. level 2), select the “Exit” option. Thedisplay will prompt for confirmation of the Level 3 password. For example:[Commission Menu 1]Please Enter Your PasswordNext MenuIf the password is incorrect (this will be indicated) or if the password is not entered within 5-seconds, the displaywill revert to the Commission Level Menu and level-2 will not be entered.After commissioning, the panel must always be returned to level 2 (or level 1) to give normal fire coverage.3.3.10 DisableThis function is the same as User Level 2 function – refer to User Manual for further information.The following options can be disabled: Zones / Inputs Outputs GroupsPPCCOONNLLYYIf beacon outputs are configured so that they can be independently disabled /enabled, then configure one of the front panel “Function” LED indicators to indicatethe disabled state of these devices.3.3.11 EnableThis function is the same as User Level 2 function – refer to User Manual for further information.The following options can be disabled: Zones / Inputs Outputs Groupswww.acornfiresecurity.comwww.acornfiresecurity.com