24V motor control device for flush box mounting - Version 1.1 Instruction manual 13/226Initial operationw w w . b a i e r - g m b h . d e6.1 ConfigurationN O T I C EOvertightened potentiometerDamage of control device may result in malfunction.Potentiometers have a right and a left stop, which must notbe overtightened. Adjust potentiometer only with low force and with anappropriate screw driver.HintChanges in configuration when the initial operation is done, will forcethe control device to perform a new initial operation. Perform initial operation, refer to chapter 6.26.1.1 Tolerance of power operated shutdownIn some cases the drive will not shut down correctly during or after initial operation.Or the drive stops, before it has reached the end position. This particularly happens,when a very heavy or a very lightweight wing is used.N O T I C EMotor overloadDamage of components by motor overload. Check after any change of configuration, if the controldevice shuts down correctly. Do not set tolerance too high.When the drive stops early Turn potentiometer 1 clockwise Drive switches off laterWhen the drive does not stop Turn potentiometer 1 counterclockwise Drive switches off soonerHintAfter a maximum time of 5 minutes, the drive switches off in each case.Increase toleranceDecrease tolerance