4E. ELECTRICAL CONNECTION:Install according to the spacing requirements listed in the installation section of this manual. We stronglyrecommend having a competent professional install this equipment. A licensed electrician should makethe electrical connections and connect power to the unit. Local codes should always be used whenconnecting these units to electrical power. In the absence of local codes, use the latest version of theNational Electrical Code.Note: For supply connections use No. 6 AWG wires suitable for at least 90°C.SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR WHENINSTALLED WITH LEGS OR CASTERS PROVIDED.! !CAUTION: DO NOT SET THE OVEN WITH ITS BACK FLAT AGAINST THEWALL. IT WILL NOT OPERATE PROPERLY UNLESS THERE IS AT LEASTTHREE INCHES BREATHING SPACE BEHIND THE OVEN! !NOTICE: LOCAL CODES REGARDING INSTALLATION VARY GREATLYFROM ONE AREA TO ANOTHER. THE NATIONAL FIRE PROTECTIONASSOCIATION, INC., STATES IN IT’S NFPA 96 LATEST EDITION THAT LOCALCODES ARE “AUTHORITY HAVING JURISDICTION” WHEN IT COMES TOREQUIREMENTS FOR INSTALLATION OF EQUIPMENT. THEREFORE,INSTALLATIONS SHOULD COMPLY WITH ALL LOCAL CODES.! !C. INSTALLATION WITH CASTERS (OPTIONAL):Four casters (two with wheel brakes) and the mounting hardware are packed and included in theshipment if ordered. Install casters with wheel brakes on the front of the unit. Installation must conformto UL 197: Electrical Supply Connections For Permanently Connected Appliances. It requires thatpermanently connected appliances with casters be provided with a means for securing the appliance tothe building structure to limit the movement of the appliance.Oven Restraint: When casters are installed on either a single or double unit, a fixed restraint must beused to limit the movement of the appliance without depending on or transmitting stress to the electricalconduit. The restraint (a heavy-gauge cable) should be attached to the rear legs of the oven on whichcasters are mounted. If disconnection of the restraint is necessary, the restraint must be reconnectedafter the oven has been repositioned in its permanent location. The appliance shall be installed usingflexible conduit.D. LOCATION AND MINIMUM CLEARANCES:Move the oven to its final location keeping the minimum clearance from the back of the oven to the wall.This clearance is necessary for safe operation and to provide proper air flow.Under Ventilation HoodRIGHT WALL 1”LEFT WALL 1”REAR WALL 3”MINIMUM CLEARANCES FROM COMBUSTIBLE AND NONCOMBUSTIBLE CONSTRUCTION