Operation 4‐5MN2408Inputs and OutputsAny Binary input or output can be configured to any controller terminal Inputs are BI1 - BI6,Outputs are BO1 - BO6) or changed to different function by LiteEdit software.There is fixed 1 sec delay when any binary input is configured as protection.Table 4‐11 Binary InputsAlarm Alarm type Warning or Shut downAlarm active All the time, or Engine running onlyRem start/stop External request for engine run. AUT mode only.Emergency stop If the input is opened, shut down is immediately activated. Input isinverted (normally closed).Rem start/stop External request for engine run. AUT mode only.Table 4‐12 Binary outputsStarter (relay output) The closed relay energizes the starter motor.The relay opens if: The firing speed is reached or Maximum time of cranking is exceeded or Request to stop occursFuel solenoid (relay output) Closed output opens the fuel solenoid and enables the engine start.The output opens if:Emergency stop occurs orCooled gen-set is stopped orIn pause between repeated startsPrestart Output is closed prior to the engine start (Prestart) and opens whenSTART RPM speed is reached.During repeated crank attempts the output is closed too.The output could be used for pre-glow, pre-heat or prelubrication.Common Sd Output closes when any shut-down alarm appears.The output opens, if alarm is not active and FAULT RESET is pressed.Used for shunt trip.