www.balluff.com 317 Process Data7.2. Process DataOutputsThe output data size is 134 bytes. Take a look at the tables below for the allocation of theprocess data outputs.BNI EIP-502-105-R015Byte Module part Description0…5 Standard I/O ports Process data outputs at the standard inputs6…37 IO-Link port 1 Process data outputs at IO-Link port 138…69 IO-Link port 2 Process data outputs at IO-Link port 270…101 IO-Link port 3 Process data outputs at IO-Link port 3102…133 IO-Link port 4 Process data outputs at IO-Link port 4BNI EIP-508-105-R015Byte Module part Description0…5 Standard I/O ports Process data outputs at the standard inputs6…37 IO-Link Port 0 Process data output at IO-Link port 038…69 IO-Link port 1 Process data output at IO-Link port 170…101 IO-Link port 2 Process data output at IO-Link port 2102…133 IO-Link port 3 Process data output at IO-Link port 3134…165 IO-Link port 4 Process data output at IO-Link port 4166…197 IO-Link port 5 Process data output at IO-Link port 5198…229 IO-Link port 6 Process data output at IO-Link port 6230…261 IO-Link port 7 Process data output at IO-Link port 7Standard OutputDataBNI EIP-502-105-R015 and BNI EIP-508-105-R015Byte Bit Description7 6 5 4 3 2 1 00 O32 O34 O22 O24 O12 O14 O02 O04Output dataO04 Output at port 0, pin 4To use this function at an IO-Link port, the port has to beconfigured as an output.1 O72 O74 O62 O64 O52 O54 O42 O442 R32 R34 R22 R24 R12 R14 R02 R04 RestartRestart of the output after ashort-circuit is detected3 R72 R74 R62 R64 R52 R54 R42 R444 0 0 0 0 0 0 0 0 Reserved5 0 0 0 0 0 DL GO RODisplay control systemDL: Display disabled / PLClockGO: Green display LEDilluminatesRO: Red display LED illumi-natesIO-Link OutputDataBNI EIP-502-105-R015 and BNI EIP-508-105-R015Byte Bit Description7 6 5 4 3 2 1 06…37 IO-Link port 0 output data… The data of the other IO-Link ports are structured identically and described in the follow-ing.