Cleaning proceduresCAUTIONStainless steel parts can be sharp.Avoid risk for cutting injury by wearing the proper protective equipment !WATER DISTRIBUTION PIPE AND STRAINERSThe water distribution piping of the adiabatic pre-cooling section is supplied with in line water filters, filtering waterparticles from the incoming water.Some solids in the water may accumulate in the water distribution header and need to be rinsed out at least twice ayear. Also the city water filters or strainers need to be cleaned out at least once per month as follows: removewater filter access cap, remove strainer mesh and rinse mesh with clean water.Water filterThe recommended procedure for cleaning of the water distribution header is:1. Remove all the pre-cooling media from the pre-cooler section to give access to the water distribution headerends. Refer to "Cleaning procedures", section "Adiabatic pre-cooling media", subsection "Removal andreplacement".2. Unscrew the flexible sleeve connection by loosening the sleeve clamps. Use a 7 mm spanner or otherappropriate tool.W W W . B A L T I M O R E A I R C O I L . E U22