* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.4.6 Setting the Modbus Slave ID on the I/O Base BoardOnly DXM150-Sx and SxR2 Modbus Slave models require that the Modbus Slave ID to be adjusted on the I/O base board.The DXM150-Sx Wireless Modbus Slave devices use DIP switch J and rotary dial K to set the Modbus slave ID. The devicecan use a Modbus register 6804 in the I/O board to access the full range of Modbus Slave IDs.On the DXM150-Sx Wireless Modbus Slave models, use rotary dial K to select the lower digit of the Modbus Slave ID.4.6.1 DXM150-Sx Wireless Modbus Slave ModelsDIP Switch location J defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM1xx-Sx andDXM1xx-SxR2 models.SettingsLocation J DIP Switches1 2 3 4Modbus Slave ID set to 11 through 19 OFF OFFModbus Slave ID set to 20 through 29 ON OFFModbus Slave ID set to 30 through 39 OFF ONModbus Slave ID set to 40 through 49 ON ONNot Used -Modbus Slave Configuration (S1 model only) 2 ONI2C Processor Communication OFFRotary dial location K and DIP Switch location J set the Modbus Slave IDs.DIP Switches J Location K Rotary Dials — Position 0 through 91 2 0 1 2 3 4 5 6 7 8 9OFF OFF x 3 11 12 13 14 15 16 17 18 19ON OFF 20 21 22 23 24 25 26 27 28 29OFF ON 30 31 32 33 34 35 36 37 38 39ON ON 40 41 42 43 44 45 46 47 48 49DXM150-Sx Wireless Modbus Slave ExampleTo set the DXM150-Sx Wireless Modbus Slave to a Modbus Slave ID of 25, set the following:Location J DIP switches set to: 1= ON, 2=OFFRotary dial set to 5The DIP switch sets the upper digit of the slave ID to 2 while the rotary dial sets the lower digit to 5.4.6.2 Setting the DXM I/O Board Modbus Slave ID using Modbus RegistersWrite to the I/O board's Modbus register 6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).• For the DXM150-Sx Wireless Modbus Slave model, rotary dial K should be in the zero position to use the Modbusregister slave ID.4.6.3 I/O Board JumpersHardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the devicebefore you change jumper positions.2 Must be in the ON position for the -S1 model)3 Uses value in Modbus register 6804.DXM150-Sx Wireless Modbus Slavewww.bannerengineering.com - Tel: +1.763.544.3164 21