1-6 BE1-40Q General Information 9171500990 Rev MTarget IndicatorAn electronically latched, manually reset target indicator is optionally available to indicate closure of thetrip output contact. Either an internally operated or a current operated target may be specified. Aninternally operated target should be selected when a normally closed (NC) output contact is specified.Current Operated TargetMinimum Rating: 200 mA flowing through the trip circuitContinuous Rating: 3 A1 Second Rating: 30 A2 Minute Rating: 7 AType TestsShock: Withstands 15 G in each of three mutually perpendicular planeswithout structural damage or performance degradation.Vibration: Withstands 2 G in each of three mutually perpendicular planes,swept over the range of 10 to 500 Hz for a total of six sweeps, 15minutes each sweep, without structural damage or degradation ofperformance.Dielectric Strength: Tested in accordance with IEC 255-5 and IEEE C37.90. All circuits toground: 2,121 Vdc. Input to Output circuits: 1,500 Vac/2,121 Vdc.Radio Frequency Interference: Maintains proper operation when tested for interference inaccordance with IEEE C37.90.2-1987, Standard WithstandCapability of Relay Systems to Radiated ElectromagneticInterference from Transceivers.Surge Withstand Capability: Qualified to IEEE C37.90.1-1989, Standard Surge WithstandCapability (SWC) Tests for Protective Relays and Relay Systems.PhysicalTemperatureOperating Range: –40 to 70°C (–40 to 158°F)Storage Range: –65 to 100°C (–85 to 212°F)Weight: 13.5 lb (6.12 kg)Case Size: S1 (Refer to Section 4 for case dimensions.)Agency Recognition/CertificationUL Recognition: UL recognized per Standard 508, File E97033NOTE: Output contacts are not UL recognized for voltages greaterthan 250 volts.GOST-R Certification: GOST-R certified per the relevant standards of Gosstandart ofRussia.