SERVICE2 TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUERESET 20 mA Power Source 0/1 0 = EXTERNAL, 1 = INTERNAL 0DEMAND 20 mA Power Source 0/1 0 = EXTERNAL, 1 = INTERNAL 0CHWS Temp Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0CHWS Temp Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)CHWR Temp Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0CHWR Temp Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)Reset Temp Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Reset Temp Alert –40 to 245(–40 to 118)DEG F(DEG C)245(118)Spare Temp 1 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 1 Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)Spare Temp 2 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 2 Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)Spare Temp 3 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 3 Alert –40 to 245(–40 to 118)DEG F(DEG C)245(118)SPARE 1 20 mA Power Source 0/1 0 = EXTERNAL, 1 = INTERNAL 0SPARE 2 20 mA Power Source 0/1 0 = EXTERNAL, 1 = INTERNAL 0Spare Temp 4 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 4 Alert –40 to 245(–40 to 118)DEG F(DEG C)245(118)Spare Temp 5 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 5 Alert –40 to 245(–40 to 118)DEG F(DEG C)245(118)Spare Temp 6 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 6 Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)Spare Temp 7 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 7 Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)Spare Temp 8 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 8 Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)Spare Temp 9 Enable 0 to 4 0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,3 = HIGH ALARM, 4 = LOW ALARM 0Spare Temp 9 Alert –40 to 245(–40 to 118) DEG F(DEG C) 245(118)CL-9