41INSTALL ACCESSORY ISOLATION (if required) —Uneven floors or other considerations may dictate the use ofaccessory soleplates (supplied by Carrier for field installation)and leveling pads. Refer to Fig. 48.Level machine by using jacking screws in isolation sole-plates. Use a level at least 24-in. (610 mm) long.For adequate and long lasting machine support, propergrout selection and placement is essential. Carrier recommendsthat only pre-mixed, epoxy type, non-shrinking grout be usedfor machine installation. Follow manufacturer’s instructions inapplying grout.1. Check machine location prints for required groutthickness.2. Carefully wax jacking screws for easy removal fromgrout.3. Grout must extend above the base of the soleplate andthere must be no voids in grout beneath the plates.4. Allow grout to set and harden, per manufacturer’sinstructions, before starting machine.5. Remove jacking screws from leveling pads after grouthas hardened..OUTSIDE EDGE O1'-3 7/8"[403mm]CONDENSER TUBEOUTSIDE EDGE OF(TYPICAL BOTH ENCOOLER TUBESH(TYPICAL BOTH E[997mm]3'-3 1/4"Y*[387mm]TYPICAL1'-3 1/4"14'-9"[4496mm]SUPPORT PLATEX*[4286mm]14'-0 3/4"[105mm]XTYPICAL[13mm]0'-0 1/2"[213mm]0'-8 3/8"0'-4 1/8"0'-9"YTYPICAL[229mm]0'-3"[76mm]ACCESSORY SOLEPLATETYPICAL0'-3 1/2"[89mm][610mm]2'-0"[38mm]0'-1 1/2"TYPICALCL COOLER & COMPRESSORREARFRONTSUCTION END DISCHARGE ENDCL CONDENSERFig. 45 — 23XRV Frame Size B Machine Footprinta23-1684*See Fig. 47 or 48.IMPORTANT: Chiller support plates must be levelwithin 1/2 in. from one end to the other end of the heatexchangers for effective oil reclaim system operation.VIEW Y-Ya23-46NOTES:1. Dimensions in ( ) are in millimeters.2. Isolation package includes 4 shear flex pads.Fig. 47 — Standard Isolation/LEGLEGENDNOTES:1. Dimensions in ( ) are in millimeters.2. Accessory (Carrier supplied, field installed) soleplate pack-age includes 4 soleplates, 16 jacking screws and levelingpads.3. Jacking screws to be removed after grout has set.4. Thickness of grout will vary, depending on the amount nec-essary to level chiller. Use only pre-mixed non-shrinkinggrout,Ceilcote 748 OR Chemrex Embeco 636 Plus Grout 0-1½(38.1) to 0-2¼ (57) thick.HRS — Hot Rolled SteelVIEW X-XACCESSORY SOLEPLATE DETAILa19-1109a19-1110Fig. 48 — Accessory Isolation