25Advanced Settings• Hold the “MENU (SW4)” button down for five secondsto enter the menu.• Press “UP(SW5) / DOWN(SW6)” button to select andset the item. When the number is chosen, the number willflash. Then press “OK(SW3)” to confirm and set the nextnumber. Use Table 19 below as reference.• Hold “OK(SW3)” again to exit the main menu.Table 19 — List of Menu FunctionsSnow-Blowing Function1. Press SW5 button on spot check box of the headeroutdoor unit to enter the snow-blowing function. It willdisplay “Sn0” for 15 seconds.2. Press SW5 button again to exit the snow-blowingfunction. It will display “Sn1” for 15 seconds.The snow-blowing modes can be selected through S11 dipswitch on spot check box as shown in Fig. 42..Fig. 42 —S11 - Snow-Blowing ModesIf the unit receives a startup signal, it will exit the snow-blowing function.Pre-Start Check• Check that the refrigerant pipe line and communicationwire with indoor and outdoor unit have been connectedto the same refrigeration system.• Outdoor units require either 208/230-3-60 or 460-3-60power. Verify that the power and phase requirements arecorrect and all three legs are present.• Check that power source’s voltage is within 10% of therated voltage.• Check and confirm that the power and control wire arecorrectly connected.• Check that the wired controllers are properly connected.• Before powering on, confirm there is no short circuit foreach line.• Check that all units have passed a nitrogen pressure testfor 24 hours.• Provide the customer accurate “as-built” drawings anddocuments, including actual piping lengths andlocations, unit addresses, settings, etc.• Ensure additional refrigerant charge calculations arecorrect, and that the system is charged accordingly.• Energize outdoor units for at least 24 hours beforestartup to ensure proper oil temperature.• Ensure all refrigerant valves on outdoor units are fullyopen. Ensure oil balancing valves are open for 2 and 3-module systems. If these valves are not fully open,equipment damage may occur.SYMBOL FUNCTION ITEM DESCRIPTION_n1_Specialfunction fordebugging_n12 Forced cooling (62.6Fof IDU)_n13 Forced heating (86F ofIDU)_n14 Cooling test_n15 Heating Test_n2_Refrigerantrecyclefunction_n21 Refrigerant recycled tooutdoor units_n22 Refrigerant recycled toindoor units_n23 Refrigerant recycled topiping_n26 Maintenance operation_n3_ Malfunctionquery_n31 Historical malfunctionquery_n32 Clear the historical mal-function_n4_ Night timesetting_n41 6/10H (default)_n42 6/12H_n43 8/10H_n44 8/12H_n5_ Silent modesetting_n51 Night silent mode_n52 Silent mode_n53 Super silent mode_n54 Silent mode off (default)_n8_ Static pressuremode setting_n81 Standard static pressuremode (default)_n82 Low static pressuremode (reserved)_n83 Medium static pressuremode (reserved)_n84 High static pressuremode (reserved)_nb_ Temperatureunit setting_nb1 Temperature unit(Celsius)_nb2 Temperature unit(Fahrenheit)_nC_T4 sensor(outdoortemperature)threshold toenableAuxiliary Heat.Aux heat willenable whenoutdoortemperaturefalls 1.8 Fbelow thistemperature._nC1 Auxiliary heat disabled_nC2 5 °F_nC3 15 °F_nC4 25 °F_nC5 35 °F_nC6 45 °F_nC7 55 °F_nC8 65 °FMode Heavy SnowModeLight SnowModeS11