15AIR THROW DATAUnit Size Approximate Air Throw ft. (m)Low Medium High Turbo9 K 18 (5.5) 21 (6.4) 23 (7.0) 28 (8.5)12 K 20 (6.1) 23 (7.0) 25 (7.6) 30 (9.1)18 K 22 (6.7) 27 (8.2) 33 (10.1) 39 (11.9)24 K 25 (7.6) 29 (8.8) 34 (10.4) 42 (12.8)30 K 35 (10.7) 37 (14.3) 40 (12.1) NA36 K 37 (11.3) 40 (12.1) 45 (13.7) NASOUND RATINGSOutdoor UnitsModel Number Sound Power dBA Sound Pressure dBA38GVC009 --- --- ---1 63 5338GVC012 --- --- ---1 65 5538GVC012 --- --- ---3 62 5238GVC018 --- --- ---3 66 5638GVC024 --- --- ---3 63 5338GVC036 --- --- ---3 75 6538GVQ009 --- --- ---1 63 5338GVQ012 --- --- ---1 65 5538GVQ012 --- --- ---3 62 5238GVQ018 --- --- ---3 66 5638GVQ024 --- --- ---3 66 5638GVQ030 --- --- ---3 72 6238GVQ036 --- --- ---3 75 65Indoor UnitsModel NumberLow Medium High TurboSoundPower dBASoundPressuredBASoundPower dBASoundPressuredBASoundPower dBASoundPressuredBASoundPower dBASoundPressuredBA40GVC009 --- --- ---1 42 32 45 35 47 37 50 4040GVC012 --- --- ---1 42 32 45 35 47 37 50 4040GVC012 --- --- ---3 38 28 43 33 49 39 54 4440GVC018 --- --- ---3 44 34 48 38 53 43 58 4840GVC024 --- --- ---3 44 34 49 39 53 43 59 4940GVC036 --- --- ---3 63 53 66 56 69 59 --- ---40GVQ009 --- --- ---1 (cool/heat) 42/42 32/32 45/45 35/35 47/47 37/37 50/50 40/4040GVQ012 --- --- ---1 (cool/heat) 42/42 32/32 45/45 35/35 47/47 37/37 50/50 40/4040GVQ012 --- --- ---3 (cool/heat) 38/38 28/28 43/43 33/33 49/49 39/39 54/54 44/4440GVQ018 --- --- ---3 (cool/heat) 44/44 34/34 48/48 38/38 53/53 43/43 58/58 48/4840GVQ024 --- --- ---3 (cool/heat) 44/44 34/34 49/49 39/39 53/53 43/43 59/59 49/4940GVQ030 --- --- ---3 (cool/heat) 58/58 48/48 64/64 54/54 67/67 57/57 --- ---40GVQ036 --- --- ---3 (cool/heat) 63/63 53/53 66/66 56/56 69/69 59/59 --- ------ = N/ANOTES:1. Sound power ratings are per AHRI 270 and AHRI 3502. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.ELECTRICAL DATACooling OnlyUnitSizeSystem Voltage OperatingVoltage* Compressor Outdoor Fan Indoor Fan{ MCAMAXFUSE/CB AmpVOLT--- PH--- HZ MAX / MIN RLA LRA FLA W VOLTS FLA W9 K 115 ---1 --- 60 127/103 9.76 25.00 0.17 30 115 0.38 15 13 2012 K 115 ---1 --- 60 127/103 11.20 25.00 0.17 30 15 2512 K 208/230 ---1 ---60 253/187 7.30 16.50 0.25 21 208/230 0.19 15 10 1518 K 208/230 ---1 ---60 253/187 10.86 27.00 0.62 60 208/230 0.32 20 15 2524 K 208/230 ---1 ---60 253/187 11.71 41.00 0.62 60 208/230 0.45 35 16 2536 K 208/230 ---1 ---60 253/187 16.92 67.00 0.73 170 208/230 0.47 60 24 35Heat Pump9 K 115 ---1 ---60 127/103 9.76 20.00 0.17 30 115 0.38 15 13 2012 K 115 ---1 ---60 127/103 11.20 20.00 0.17 30 15 2512 K 208/230 ---1 ---60 253/187 7.30 16.50 0.25 21 208/230 0.19 15 10 1518 K 208/230 ---1 ---60 253/187 10.86 27.00 0.62 60 208/230 0.32 20 15 2524 K 208/230 ---1 ---60 253/187 11.71 41.00 0.62 60 208/230 0.45 35 16 2530 K 208/230 ---1 ---60 253/187 13.45 40.00 0.45 100 208/230 0.45 40 20 3036 K 208/230 ---1 ---60 253/187 17.50 67.00 0.73 170 208/230 0.47 60 24 40* Permissible limits of the voltage range at which the unit will operate satisfactorily{ Indoor fan powered from outdoor unit.LEGENDFLA --- Full Load AmpsLRA --- Locked Rotor AmpsMCA --- Minimum Circuit AmpsRLA --- Rated Load Amps38/40GVC(Q)