16PERFORMANCE DATACOOLING CAPACITIES38HDR018 / 40QAC024*Temp ° F(° C)Air EnteringCondenser (Edb)Air Entering Evaporator --- Cfm/BF320/0.02 400/0.03 500/0.03Air Entering Evaporator --- Ewb ° F (° C)57(13.9)62(16.7)67(19.4)72(22.2)57(13.9)62(16.7)67(19.4)72(22.2)57(13.9)62(16.7)67(19.4)72(22.2)55(12.8)TCG 17.2 18.7 20.1 21.5 17.7 19.1 20.5 21.8 18.1 19.5 20.8 22.1SHG 16.8 15.0 12.9 10.7 17.2 15.7 13.3 10.9 18.1 16.4 13.8 11.2TC 17.0 18.5 19.9 21.3 17.4 18.8 20.2 21.6 17.8 19.3 20.6 21.9kW 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.95 0.94 0.94CMP 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.76 0.75 0.76 0.75 0.76LDB 46.3 50.2 54.9 59.7 49.0 52.1 56.8 61.4 51.3 54.2 58.7 63.1LWB 41.6 46.9 52.5 58.2 43.0 48.4 54.0 59.7 44.5 49.9 55.4 61.165(18.3)TCG 16.3 18.2 19.6 21.1 17.0 18.6 20.0 21.4 17.7 18.9 20.3 21.6SHG 16.3 14.9 12.8 10.6 17.0 15.5 13.2 10.8 17.7 16.4 13.7 11.1TC 16.1 17.9 19.4 20.8 16.8 18.3 19.7 21.1 17.4 18.7 20.1 21.4kW 1.06 1.05 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06CMP 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.88LDB 47.2 50.5 55.1 59.8 49.4 52.3 56.8 61.5 51.9 54.2 58.7 63.2LWB 42.5 47.4 52.9 58.6 43.6 48.8 54.3 60.0 44.8 50.3 55.8 61.475(23.9)TCG 15.6 17.4 19.0 20.5 16.4 17.8 19.4 20.8 17.1 18.2 19.7 21.1SHG 14.9 14.6 12.6 10.4 16.4 15.3 13.1 10.7 17.1 16.2 13.7 11.0TC 15.4 17.2 18.8 20.3 16.2 17.5 19.1 20.6 16.9 17.9 19.5 20.9kW 1.17 1.19 1.19 1.19 1.18 1.18 1.19 1.19 1.18 1.19 1.19 1.19CMP 0.99 1.00 1.00 1.00 0.99 1.00 1.00 1.01 1.00 1.00 1.00 1.01LDB 50.3 51.1 55.4 60.1 50.4 52.7 57.0 61.7 52.8 54.4 58.7 63.3LWB 43.3 48.1 53.4 59.0 44.1 49.4 54.8 60.3 45.3 50.8 56.1 61.785(29.4)TCG 14.8 16.5 18.2 19.8 15.6 16.9 18.6 20.1 16.4 17.2 18.9 20.5SHG 14.8 13.9 12.2 10.2 15.6 14.8 12.9 10.5 16.4 15.8 13.6 10.9TC 14.5 16.2 18.0 19.6 15.4 16.6 18.3 19.9 16.1 17.0 18.6 20.2kW 1.30 1.32 1.33 1.33 1.31 1.32 1.33 1.33 1.32 1.33 1.33 1.34CMP 1.12 1.13 1.15 1.15 1.13 1.14 1.15 1.15 1.14 1.14 1.15 1.15LDB 50.4 52.4 56.1 60.5 52.0 53.6 57.4 62.0 53.9 55.0 59.0 63.5LWB 44.1 49.0 54.1 59.5 44.9 50.2 55.3 60.7 45.8 51.4 56.6 62.095(35)TCG 14.2 15.4 17.2 19.0 14.7 15.7 17.6 19.3 15.5 16.1 18.3 19.6SHG 14.2 13.3 11.8 9.8 14.7 14.2 12.5 10.2 15.5 15.2 13.5 10.7TC 13.9 15.2 17.0 18.7 14.5 15.5 17.3 19.0 15.2 15.9 18.0 19.3kW 1.53 1.54 1.56 1.57 1.53 1.54 1.57 1.57 1.54 1.55 1.57 1.57CMP 1.34 1.35 1.37 1.38 1.35 1.36 1.38 1.39 1.36 1.36 1.38 1.39LDB 51.6 53.6 57.0 61.3 53.6 54.7 58.1 62.5 55.4 56.0 59.5 63.8LWB 44.7 49.9 54.9 60.1 45.6 51.1 56.0 61.3 46.5 52.2 57.2 62.5105(40.6)TCG 13.3 14.2 16.0 17.9 13.9 14.5 16.3 18.2 14.5 15.1 16.6 18.5SHG 13.3 12.7 11.2 9.4 13.9 13.5 11.8 9.8 14.5 13.4 12.6 10.3TC 13.1 13.9 15.7 17.6 13.6 14.2 16.0 17.9 14.3 14.9 16.4 18.2kW 1.60 1.61 1.63 1.66 1.61 1.61 1.64 1.66 1.62 1.62 1.64 1.66CMP 1.42 1.43 1.45 1.47 1.42 1.43 1.45 1.47 1.43 1.43 1.46 1.48LDB 53.4 54.8 58.2 62.0 55.1 56.0 59.3 63.2 57.0 58.9 60.4 64.4LWB 45.5 51.0 55.9 60.9 46.4 52.0 56.9 62.0 47.2 52.9 58.0 63.1115(46.1)TCG 12.3 12.9 14.6 16.5 12.8 13.3 14.9 16.8 13.4 13.8 15.2 17.1SHG 12.3 11.6 10.4 8.9 12.8 12.1 11.1 9.3 13.4 12.5 11.9 9.8TC 12.1 12.7 14.4 16.3 12.6 13.1 14.7 16.6 13.2 13.5 14.9 16.9kW 1.77 1.77 1.79 1.83 1.78 1.77 1.80 1.83 1.78 1.79 1.80 1.84CMP 1.58 1.58 1.61 1.64 1.59 1.59 1.61 1.65 1.60 1.60 1.62 1.66LDB 55.4 57.0 59.7 63.1 57.0 58.5 60.6 64.0 58.7 60.4 61.5 65.1LWB 46.5 52.1 56.9 61.8 47.3 52.9 57.9 62.8 48.1 53.8 58.9 63.8125(51.7)TCG 11.2 11.6 13.1 14.9 11.7 11.8 13.3 15.2 12.3 12.3 13.6 15.5SHG 11.2 10.8 9.8 8.2 11.7 11.8 10.5 8.7 12.3 12.3 11.2 9.2TC 11.0 11.3 12.9 14.7 11.5 11.5 13.1 14.9 12.0 12.0 13.3 15.2kW 1.96 1.94 1.97 2.01 1.95 1.95 1.97 2.01 1.96 1.96 1.98 2.01CMP 1.77 1.76 1.78 1.82 1.77 1.76 1.79 1.83 1.78 1.77 1.79 1.83LDB 57.7 58.6 60.9 64.4 59.0 59.1 61.7 65.2 60.6 60.7 62.6 66.1LWB 47.6 53.2 58.1 62.9 48.2 53.9 58.9 63.8 48.9 54.7 59.8 64.7Rating Condition.Not recommended for long--- term operationBF --- Bypass FactorCMP --- CompressorEdb --- Entering Dry BulbEwb --- Entering Wet BulbkW --- Total PowerLDB --- Leaving Dry BulbLWB --- Leaving Wet BulbSHG --- Gross Sensible Capacity (1000 Btuh)TC --- Total Net Cooling Capacity (1000 Btuh)TCG --- Gross Cooling Capacity (1000 Btuh)* The 40QAC024 unit must be field configured to an 018 size unit by changing themotor speed fan tap plug. Refer to Installation Instructions for more details.NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The SHG is based on 80_F (26.7_C) edb temperature of air entering indoor coil.Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.Above 80_F (26.7_C) edb, add (corr factor x cfm) to SHG.Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).40QAC/38HDR -- 40QAQ/38QRR