GB - 340SMC---NE N G L I S HTechnical dataTable III - Electrical data (heat pump) - 38YY - 38BH + 40SMC---N38YY - 38BH 09 12 18 24 28 36 48 60+ + + + + + + + +40SMC---N 009 012 018 024 028 036 048 060Operation voltage V/Ph/Hz m m m m m/l m/l m/l lCONSUMPTIONNominal (on cooling) * kW 1,00 1,22 1,79 2,20 2,77 3,48 4,0 5,15Amp 4,52 5,52 8,10 10,10 12,53/4,77 15,75/5,24 13,5/7,95 18,4/10,6Nominal (on heating) ** kW 0,92 1,10 1,67 2,20 2,61 2,74 3,80 4,65Amp 4,16 4,97 7,56 10,10 11,80/3,93 12,40/4,13 13,7/7,9 17,2/9,90Máximum (on coolig) *** kW 1,20 1,46 2,15 2,69 3,32 4,17 4,43 6,58Amp 5,43 6,60 9,73 12,17 15,02/5,0 18,87/6,28 14,8/8,53 23,6/13,58Máximum (on heating) **** kW 1,10 1,32 2,00 2,04 3,13 3,29 5,11 6,0Amp 4,98 5,97 9,05 9,23 14,16/4,71 14,89/4,95 17,1/9,84 21,5/12,38On short circuit Amp 28,5 35,0 51,5 78,0 84,5/47,5 108,0/49,0 103,0/53,0 124,0/64,0NOTAS:* Outdoor dry bulb temp. = 35 o C; Indoor wet bulb temp. = 19 o C.** Outdoor wet bulb temp. = 6 o C; Indoor dry bulb temp. = 20 o C.*** Outdoor dry bulb temp. = 43 o C; Indoor wet bulb temp. = 23 o C.**** Outdoor wet bulb temp. = 18 o C; Indoor dry bulb temp. = 27 o C.m Outdoor unit operation voltage 230V ~ 50Hzl Outdoor unit operation voltage 400V 3N~ 50HzTable IV: Operating limits -40SMC---N (cooling only)AIR TEMPERATUREZONE DRY BULB WET BULBCOOLING OPERATIONIndoor:Maximum +32°C +23°CMinimum +21°C +15°COutdoor:Maximum +43°C –Minimum +15°C * –* With optional head pressure control, the unit can operate at temperaturesbelow +15°C.External static pressure009 - 012 - 01840SMC---N 024 - 036 048 - 060Maximumexternalstatic 70 160pressure (Pa)Table V: Operating limits -40SMC---N (heat pump)AIR TEMPERATUREZONE DRY BULB WET BULBCOOLING OPERATIONIndoor:Maximum +32°C +23°CMinimum +21°C +15°COutdoor:Maximum +43°C –Minimum +15°C * –HEAT PUMP OPERATIONIndoor:Maximum +27°C –Outdoor:Maximum +24°C +18°CMinimum -10°C –* With optional head pressure control, the unit can operate at temperaturesbelow +15°C.