42PQV/38VBHGB - 4DEBACFAMinimum clearances and operating limitsModel 009-012A mm 50B mm 100C mm 400D mm 50E mm 300F mm 400Maximum conditions outdoor temperature 46°Cindoor temperature 32°C d.b.; 23°C w.b.Minimum conditions outdoor temperature 15°Cindoor temperature 21°C d.b.; 15°C w.b.Maximum conditions outdoor temperature 24°C d.b.; 18°C w.b.indoor temperature 27°C d.b.Minimum conditions outdoor temperature –10°C d.b.Nominal single-phase voltage 220V-240V, 50/60HzOperating voltage limits min. 198V – max. 264VTable III: Operating limits (1)CoolingHeatingMains power supply Obstacle90min.1900min.100min.200min.WARNING:During heat pump operation unit will undergo several defrost cycles toeliminate ice that might possibly collect on the outdoor unit in very lowambient temperatures. In these cycles, fan speed will automatically stop,louvre(flap) will be fixed at horizontal position and cannot be varied untildefrost cycle is completed.Notes: 1. Data referred to the outdoor unit only.d.b. - dry bulb; w.b. - wet bulb