Step 8 — Adjust Factory-Installed OptionsAPOLLO CONTROL — The optional Apollo control is usedto actively monitor all modes of operation as well as indoor(evaporator) fan status, filter status, and indoor-air quality.The Apollo control is designed to work with Carrier TEMPand VVTt systems.The thermostat must be wired to the Apollo control beforestarting the unit. Refer to the Apollo control installation in-structions for information on installing the thermostat. SeeFig. 13 for Apollo location.MANUAL OUTDOOR-AIR DAMPER — The outdoor-airhood and screen are attached to the basepan at the bottom ofthe unit for shipping.Assembly:1. Determine quantity of ventilation required for building.Record amount for use in Step 8.2. Remove filter access panel by raising panel and swing-ing panel outward. Panel is now disengaged from trackand can be removed. No tools are required to removethe filter access panel. Remove outdoor-air opening panel.Save panels and screws. See Fig. 14.3. Separate hood and screen from basepan by removing thescrews and brackets securing them. Save all screws anddiscard brackets.4. Replace outdoor air opening panel with screws savedfrom Step 2.5. Place hood on front of outdoor-air opening panel. SeeFig. 15 for hood details. Secure top of hood with the6 screws removed in Step 3. See Fig. 16.6. Remove and save 8 screws (4 on each side) from sidesof the manual outdoor-air damper.7. Align screw holes on hood with screw holes on side ofmanual outdoor-air damper. See Fig. 15 and 16. Securehood with 8 screws from Step 6.8. Adjust minimum position setting of the damper bladeby adjusting the manual outdoor-air adjustment screwson the front of the damper blade. See Fig. 14. Slide bladevertically until it is in the appropriate position deter-mined by Fig. 17. Tighten screws.CONTROLWIRINGAPOLLOCONTROLWIRING TOTHERMOSTATFig. 13 — Apollo Control Factory-Installedin Typical UnitOUTDOORAIR OPENINGPANELFig. 14 — Damper Panel with ManualOutdoor-Air Damper InstalledFig. 15 — Outdoor-Air Hood DetailsHOODNOTSHOWN)Fig. 16 — Damper with Hood Attached11