45Table 16—Fan Performance 50HJ004, 50HE004 — Vertical Discharge Units; Standard Motor(Belt Drive)*AIRFLOWCFMEXTERNAL STATIC PRESSURE (in. wg0.2 0.4 0.6 0.8 1.0Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts900 566 0.14 142 690 0.23 228 791 0.32 320 879 0.42 418 957 0.52 5221000 598 0.17 173 718 0.27 267 817 0.37 366 903 0.47 471 981 0.58 5811100 632 0.21 210 748 0.31 311 844 0.42 418 929 0.53 530 1006 0.65 6461200 666 0.25 252 778 0.36 361 873 0.48 476 956 0.60 594 1031 0.72 7181300 701 0.30 300 809 0.42 418 902 0.54 540 983 0.67 665 1057 0.80 7961400 737 0.36 355 842 0.48 481 932 0.61 610 1012 0.75 744 1085 0.89 8811500 774 0.42 417 875 0.55 551 962 0.69 689 1041 0.83 830 1112 0.98 974AIRFLOWCFMEXTERNAL STATIC PRESSURE (in. wg)1.2 1.4 1.6 1.8 2.0Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts900 1029 0.63 630 1095 0.75 742 1157 0.86 859 1216 0.99 980 1272 1.11 11051000 1052 0.70 695 1118 0.82 814 1179 0.94 937 1237 1.07 1064 1293 1.20 11951100 1076 0.77 767 1141 0.90 892 1202 1.03 1021 1260 1.16 1154 — — —1200 1100 0.85 845 1165 0.98 977 1225 1.12 1112 — — — — — —1300 1126 0.94 930 1189 1.07 1069 — — — — — — — — —1400 1152 1.03 1023 1215 1.17 1168 — — — — — — — — —1500 1179 1.13 1123 — — — — — — — — — — — —NOTES:1. Bold cells indicate field-supplied drive is required.2. Maximum continuous bhp is 1.20.3. See general fan performance notes.LEGENDBhp — Brake HorsepowerWatts — Input Watts to Motor*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplieddrive.Table 17—Fan Performance 50HJ004, 50he004 — Vertical Discharge Units; High-Static Motor(Belt Drive)*AIRFLOWCFMEXTERNAL STATIC PRESSURE (in. wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts900 566 0.14 142 690 0.23 228 791 0.32 320 879 0.42 418 957 0.52 5221000 598 0.17 173 718 0.27 267 817 0.37 366 903 0.47 471 981 0.58 5811100 632 0.21 210 748 0.31 311 844 0.42 418 929 0.53 530 1006 0.65 6461200 666 0.25 252 778 0.36 361 873 0.48 476 956 0.60 594 1031 0.72 7181300 701 0.30 300 809 0.42 418 902 0.54 540 983 0.67 665 1057 0.80 7961400 737 0.36 355 842 0.48 481 932 0.61 610 1012 0.75 744 1085 0.89 8811500 774 0.42 417 875 0.55 551 962 0.69 689 1041 0.83 830 1112 0.98 974AIRFLOWCFMEXTERNAL STATIC PRESSURE (in. wg)1.2 1.4 1.6 1.8 2.0Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts900 1029 0.63 630 1095 0.75 742 1157 0.86 859 1216 0.99 980 1272 1.11 11051000 1052 0.70 695 1118 0.82 814 1179 0.94 937 1237 1.07 1064 1293 1.20 11951100 1076 0.77 767 1141 0.90 892 1202 1.03 1021 1260 1.16 1154 1314 1.30 12911200 1100 0.85 845 1165 0.98 977 1225 1.12 1112 1282 1.26 1252 1337 1.40 13951300 1126 0.94 930 1189 1.07 1069 1249 1.22 1211 1306 1.36 1356 1360 1.51 15061400 1152 1.03 1023 1215 1.17 1168 1274 1.32 1317 1330 1.48 1469 1384 1.63 16251500 1179 1.13 1123 1241 1.28 1275 1300 1.44 1431 1355 1.60 1590 1408 1.76 1752NOTES:1. Bold cells indicate field-supplied drive is required.2. Maximum continuous bhp is 1.20.3. See general fan performance notes.LEGENDBhp — Brake HorsepowerWatts — Input Watts to Motor*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplieddrive.50HE,HJ