![Carrier 50VZ Installation, Operation And Maintenance Instructions Manual pdf 5 page image](https://manuals-archive2.s3.amazonaws.com/2855883/e0b0376e21348862f8b165c98ff640085f.jpg)
5Table 2 - Electrical data50VZ (40PZ/38VZ) 015 025 030 031 040 045 055 065 075Nominal voltage ±10%* V 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400Nominal power input** kW 7.3 7.3 11.1 11.1 14.0 14.0 14.6 14.6 18.1 18.1 21.4 21.4 25.4 25.4 30.0 30.0 37.6 37.6Nominal current drawn** A 23.8 13.8 33.1 19.1 39.4 22.8 44.9 26.0 52.6 30.4 64.9 37.5 74.3 43.0 87.8 50.8 122.1 67.1Effective power input kW 6.8 6.8 10.2 10.2 13.0 13.0 13.6 13.6 16.8 16.8 19.0 19.0 22.2 22.2 26.1 26.1 33.1 33.1Effective current drawn A 21.6 12.5 30.5 17.6 37.0 21.4 41.9 24.2 56.5 32.6 57.9 33.4 70.0 40.5 76.6 44.3 102.0 59.0Starting current A 139.5 80.0 174.1 106.3 219.0 133.3 165.9 95.3 235.2 134.0 278.4 156.7 329.1 187.8 384.5 219.0 450.1 256.0Maximum power input*** kW 7.9 7.9 12.2 12.2 15.5 15.5 16.1 16.1 21.8 21.8 25.2 25.2 29.6 29.6 35.0 35.0 44.2 44.2Maximum current drawn*** A 24.2 14.0 35.5 20.5 43.2 25.0 49.5 28.6 66.6 38.5 73.1 42.2 88.8 51.3 99.7 57.6 129.5 74.8Condensing unit 38VZ 015 025 030 031 040 045 055 065 075Nominal voltage ±10%* V 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400Nominal power input + kW 6.5 6.5 10.1 10.1 12.8 12.8 13.2 13.2 16.7 16.7 19.4 19.4 23.0 23.0 26.9 26.9 34.7 34.7Nominal current drawn + A 20.6 11.9 29.9 17.3 36.6 21.2 37.8 21.9 56.2 32.5 59.4 34.3 72.7 42.0 79.1 45.7 106.6 61.6Effective power input kW 6.3 6.3 9.6 9.6 12.3 12.3 12.7 12.7 16.0 16.0 18.3 18.3 21.4 21.4 25.0 25.0 32.5 32.5Effective current drawn A 20.1 11.6 28.5 16.5 35.4 20.4 36.4 21.1 54.0 31.2 56.0 32.4 67.6 39.1 73.5 42.5 99.9 57.7Starting current A 136.7 78.4 170.1 104.0 214.1 130.5 161.1 92.5 226.9 129.2 270.9 151.2 319.2 180.9 372.2 211.9 434.2 246.8Maximum power input++ kW 7.7 7.7 11.5 11.5 14.9 14.9 15.3 15.3 20.6 20.6 24.0 24.0 29.1 29.1 33.8 33.8 43.9 43.9Maximum current drawn++ A 23.5 13.6 33.5 19.4 41.4 23.9 42.5 24.5 62.9 36.4 69.4 40.1 87.4 50.5 96.2 55.6 128.5 74.3* All units are built for 3-phase, 50 Hz supply.** Based on an outdoor air dry bulb temperature of 35°C and an indoor air wet bulb temperature of 19°C.*** Based on an outdoor air dry bulb temperature of 46°C and an indoor air wet bulb temperature of 21°C.+ Based on an outdoor air dry bulb temperature of 35°C and a dewpoint suction temperature of 7°C.++ Based on an outdoor air dry bulb temperature of 46°C and a dewpoint suction temperature of 12°C.50PZ (40PZ/38PZ) 015 025 030 031 040 045 055 065 075Nominal voltage ±10%* V 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400Nominal power input kWCooling** 7.2 7.2 11.2 11.2 13.6 13.6 14.6 14.6 18.1 18.1 21.6 21.6 25.4 25.4 30.2 30.2 38.5 38.5Heating*** 6.6 6.6 11.1 11.1 12.4 12.4 12.7 12.7 17.5 17.5 20.8 20.8 23.7 23.7 27.1 27.1 34.3 34.3Nominal current drawn ACooling** 23.7 13.7 33.2 19.2 38.4 22.2 46.0 26.6 55.0 31.8 66.1 38.2 73.3 42.4 88.0 50.9 118.5 68.6Heating*** 22.5 13.0 33.2 19.2 35.8 20.7 41.5 24.0 52.2 30.2 63.7 36.8 70.7 40.9 82.0 47.4 109.8 63.5Effective power input kWCooling 6.7 6.7 10.3 10.3 12.5 12.5 13.6 13.6 16.8 16.8 19.1 19.1 22.2 22.2 26.3 26.3 34.1 34.1Heating 6.1 6.1 10.3 10.3 11.4 11.4 11.6 11.6 16.2 16.2 18.4 18.4 20.5 20.5 23.2 23.2 29.8 29.8Effective current drawn ACooling 22.1 12.7 30.5 17.7 35.3 20.4 42.8 24.8 51.0 29.5 59.4 33.8 64.1 37.1 76.6 44.3 105.0 60.8Heating 20.8 12.0 30.8 17.8 32.9 19.0 37.9 21.9 48.3 28.0 56.4 32.6 61.2 35.4 70.2 40.6 95.4 55.2Starting current A 139.5 80.0 174.1 106.3 219.0 133.3 165.9 95.3 235.2 134.0 278.4 156.7 329.1 187.8 384.5 219.0 450.1 256.0Maximum power input kWCooling + 8.0 8.0 12.4 12.4 15.2 15.2 16.3 16.3 21.6 21.6 25.3 25.3 30.4 30.4 34.9 34.9 44.5 44.5Heating++ 7.5 7.5 13.1 13.1 15.8 15.8 14.4 14.4 20.3 20.3 23.7 23.7 28.1 28.1 32.8 32.8 41.6 41.6Maximum current drawn ACooling + 26.3 15.2 36.8 21.3 42.9 24.8 51.4 29.7 65.6 37.9 77.4 44.7 87.7 50.7 101.7 58.8 137.0 79.3Heating++ 25.6 14.8 39.2 22.7 45.6 26.4 47.1 27.2 60.6 35.0 72.6 41.9 83.8 48.5 99.2 57.4 133.2 77.0* All units are built for 3-phase, 50 Hz supply.** Based on an outdoor air dry bulb temperature of 35°C and an indoor air wet bulb temperature of 19°C.*** Based on an outdoor air wet bulb temperature of 6°C and an indoor air dry bulb temperature of 21°C.+ Based on an outdoor air dry bulb temperature of 46°C and an indoor air wet bulb temperature of 21°C.++ Based on an outdoor air dry bulb temperature of 18°C.Effective power input in accordance with EUROVENT.
PreviousNext |