14A99118Fig. 19 -- Inducer Housing Drain Tube CapRecord the code and repeat the disconnect and reconnect of the redwire, recording each code until code 11 is displayed indicating noadditional codes. After the last code is displayed or after 2 minutesin the code recall mode the control will return to normal standbymode.Step 2 — Component TestNOTE: The furnace control component test allows allcomponents to run for a short time; except the gas valve andhumidifier terminal HUM are not energized for safety reasons. TheEAC--1 terminal is energized when blower is energized. Thisfeature helps diagnose a system problem in case of a componentfailure. The component test feature will not operate if anythermostat signal is present at control and not until all time delaysare completed.To Begin Component Self-Test:ELECTRICAL SHOCK AND UNIT OPERATIONHAZARDFailure to follow this warning could result in personal injury,or death.Blower access panel door switch opens 115-v power to controlboard. No component operation can occur. Caution must betaken when manually closing this switch for service purposes.! WARNINGA99119Fig. 20 -- Funnel in Drain Tube and AntifreezeRunning Through Trap1. Remove blower access door.2. Disconnect thermostat R lead from furnace control.3. Manually close blower door switch.4. For approximately 2 sec, short (jumper) the C OM-24 v ter-minal on control to the TEST/TWIN 3/16-in. quick-connectterminal on control until LED turns off. Remove jumperfrom terminals. (See Fig.17.)NOTE: If TEST/TWIN and COM--24v terminals are jumperedlonger than 2 sec, LED will flash rapidly and ignore status coderetrieval request.Component test sequence for 2-stage furnace is as follows:a. LED will display previous status code 4 times.b. Inducer motor starts on high--speed and continues to rununtil Step g of component test sequence.c. Hot surface igniter is energized for 15 sec, then off.d. Blower motor operates on LO--HEAT speed for 10 sec.e. Blower motor operates on HI--HEAT speed for 10 sec.f. Blower motor operates on COOL speed for 10 sec.g. Inducer motor goes to low--speed for 10 sec, then stops.5. Reconnect R lead to furnace control, remove tape fromblower door switch, and re-install blower door.6. Operate furnace per instruction on outer door.7. Verify furnace shut down by lowering thermostat settingbelow room temperature.8. Verify that furnace restarts by raising thermostat settingabove room temperature.58MEC