more than 3.8-in. wc for natural gas. Make any majoradjustments by changing main burner orifices.(3.) When correct input is obtained, replace regulator sealcap. Main burner flame should be clear blue, almosttransparent. (See Fig. 12.)d. High altitude—In the United States gas input on ratingplate is for altitudes up to 2000 ft. Ratings for altitudes over2000 ft must be 4 percent less for each 1000 ft above sealevel. To obtain the adjusted altitude rating, adjust themanifold pressure (see item c) and replace the main burnerorifices as needed. Refer to National Fuel Gas CodeAppendix F, Table F-4 for proper orifice sizing at highaltitudes.e. Canadian installations only—The Canadian ratings areapproved for altitudes up to 2000 ft for natural and propanegases. High-altitude ratings are from 2000 ft to 4500 ftabove sea level. See Table 8 for nominal burner orificesize. High-altitude rating includes a 10 percent derate asrequired by Canadian standards.2. Set temperature rise.Furnace must operate within range of temperature rise speci-fied on the unit rating plate. Determine the air temperature riseas follows.a. Place duct thermometers in return and supply ducts as nearfurnace as possible. Be sure thermometers do not "see" heatexchangers so that radiant heat will not affect thermometerreadings. This is particularly important with straight-runducts.b. When thermometer readings stabilize, subtract return-airtemperature from supply-air temperature to determine tem-perature rise.c. Adjust air temperature rise by adjusting blower speed.Increase blower speed to reduce temperature rise. Decreaseblower speed to increase temperature rise.Disconnect the electrical power before changing the speedtap. A failure to follow this warning can cause personalinjury.d. To change blower motor speed selections for heating mode,remove blower motor lead from control board HEATterminal. (See Fig. 9.) Select desired blower motor speedlead from 1 of the other terminals and relocate it to HEATterminal. See Table 9 for lead color identification. Recon-nect original lead on SPARE terminal.Table 6—Model 58PAV Orifice Size and Manifold Pressure for Correct Input Rate(Tabulated Data Based on Altitude Up to 2000 Ft and 22,000 Btuh Per Burner)GASHEATVALUE(BTU/CU FT)SPECIFIC GRAVITY OF NATURAL GAS0.56 0.58 0.60 0.62 0.64 0.66 0.68 0.70 0.72OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.OrfNo.MnfldPress.8604142—3.23.6—4142—3.33.7—4142403.43.83.24140—3.53.3—4139403.73.23.44139403.83.33.53940—3.43.6—3839403.23.53.73839403.33.63.887542——3.4——4142—3.23.6—4142—3.33.7—4142403.43.83.24140—3.53.3—4139403.63.23.44139403.83.33.53940—3.33.6—3839403.23.43.789042——3.3——42——3.4——4142—3.23.6—4142—3.33.7—4142—3.43.8—4140—3.53.2—4140—3.63.3—4139403.73.23.44139403.83.33.590542——3.2——42——3.3——42——3.4——4142—3.23.6—4142—3.33.7—4142—3.43.8—4140—3.53.2—4140—3.63.3—4139403.73.23.4920 43—3.8—42—3.2—42—3.3—42—3.4—41423.23.541423.33.741423.43.841403.53.241403.63.3935 43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.23.541423.33.741423.43.841403.53.2950 43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.23.541423.33.641423.43.7965 43—3.4—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.23.541423.33.6980 44433.83.342—3.5—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.23.5995 44433.73.244433.83.443—3.5—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—1010 44—3.6—44433.73.344433.83.443—3.5—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—1025 44—3.5—44433.63.244433.73.343—3.4—43—3.5—43—3.6—43—3.7—43—3.8—43—3.2—1040 44—3.4—44—3.5—44433.63.244433.73.343—3.4—43—3.5—43—3.6—43—3.7—43—3.8—1055 44—3.3—44—3.4—44—3.5—44433.63.244433.83.343—3.4—43—3.5—43—3.6—43—3.7—1070 44—3.2—44—3.3—44—3.4—44—3.5—44433.73.244433.83.343—3.4—43—3.5—43—3.6—1085 45—3.8—44—3.2—44—3.3—44—3.4—44—3.6—44433.72.344433.83.343—3.4—43—3.5—1100 45—3.7—45—3.83.444—3.2—44—3.4—44—3.5—44—3.6—44433.73.244433.83.343—3.4—12