the impurities from the drain pan mid coil dust or dirt create theconductance. A second ground wire with appropriate terminalto the drain pan cml be used with file control to replace the aircoil ground path. The condensate sensor cml also be any opencontact that closes upon a fault comlection.Table 6 -- Thermistor Calibration PointsMINIMUM MAXIMUM NOMINALTEMP (F) RESISTANCE RESISTANCE RESISTANCE(ohm) (ohm) (ohm)78.5 9,523 9,715 9,61977,5 9,650 9,843 9,74676.5 10,035 10,236 10,13575.5 10,282 10,489 10,38533,5 30,975 31,598 31,28532.5 31,871 32,512 32,19031.5 32,653 33,310 32,98030,5 33,728 34,406 34,0651.5 80,624 82,244 81,4300.5 83,327 85,002 84,1600.0 84,564 86,264 85,410Deluxe D Control -- The Deluxe D control includes allof the control operations above in addition to the followingadvanced operations:LED INDICATORS -- There are 3 LED indicators on theDeluxe D control. See Table 7 for indicatol.'s.Status LED -- Status LED indicates the current status or modeof the Deluxe D control. The status LED light is green.Test LED -- Test LED will be activated any time the DeluxeD control is in Test mode. The test LED light is yellow.Fault LED -- Fault LED light is red. The fault LED will al-ways flash a code representing the last fault in memory. If thereis no fault in memory, the fault LED will flash code 1 on theand appear as 1 fast flash alternating with a 10-second pause.See Table 7.90.080.070.0600L50.08 40.030.0cE 20.010.00,00.0 20.0 40.0 60.0 80.0 100,0 120.0 140.0Temperature (degF)Fig. 8 -- Thermistor Nominal ResistanceEXTENDED COMPRESSOR OPERATION MONITOR --ff the compressor has been on for 4 continuous hours the con-trol will automatically turn off the compressor relay and waitthe short cycle time protection time. All appropriate safetiesincluding the low-pressure switch will be monitored. If alloperations are normal, and the compressor demand is stillpresent, the control will turn the complessor back on.STANDBY/FAN ONLY MODE -- The compressor will beoff. The fan enable, fan speed, and level.sing valve (RV) relayswill be on if inputs are present. If there is a fan 1 demand, the[an enable will immediately turn on. If there is a fan 2 demmld,file fan enable and [an speed relays will immediately turn on.NOTE: DIP switch 5 on SI (dehumidification [an mode select)does not have an effect upon [an 1 and [an 2 outputs.Table 7 -- Aquazone TM Deluxe D Control Current LED Status and Alarm Relay OperationsDESCRIPTION STATUS LED TEST LED FAULT LED ALARM RELAY(Green) (Yellow) (Red)Normal Mode On Off Flash Last Fault Code in Memory OpenCycle (closed 5 sec,Normal Mode with PM On Off Flashing Code 8 open 25 sec, ...)Deluxe D Control Off Off Off Openis Non-FunctionalTest Mode -- On Flash Last Fault Code in Memory Cycling Appropriate CodeNight Setback Flashing Code 2 -- Flash Last Fault Code in Memory --ESD Flashing Code 3 -- Flash Last Fault Code in Memory --Invalid Thermostat Inputs Flashing Code 4 -- Flash Last Fault Code in Memory --No Fault in Memory On Off Flashing Code 1 OpenHP Fault Slow Flash Off Flashing Code 2 OpenLP Fault Slow Flash Off Flashing Code 3 OpenFP1 Fault Slow Flash Off Flashing Code 4 OpenFP2 Fault Slow Flash Off Flashing Code 5 OpenCO Fault Slow Flash Off Flashing Code 6 OpenOver/Under Voltage Slow Flash Off Flashing Code 7 Open (closed after 15 minutes)HP Lockout Fast Flash Off ClosedLP Lockout Fast Flash Off ClosedFP1 Lockout Fast Flash Off ClosedFP2 Lockout Fast Flash Off ClosedCO Lockout Fast Flash Off ClosedSwapped FPI/FP2 Fast Flash Off ClosedLEGENDCO -- Condensate OverflowESD -- Emergency ShutdownFP -- Freeze ProtectionHP -- High PressureLP -- Low PressurePM -- Performance MonitorFlashing Code 2Flashing Code 3Flashing Code 4Flashing Code 5Flashing Code 6Flashing Code 9NOTES:1. If there is no fault in memory, the Fault LED will flash code 1.2. Codes will be displayed with a 10-second Fault LED pause.3. Slow flash is 1 flash every 2 seconds.4. Fast flash is 2 flashes every 1 second.5. EXAMPLE: "Flashing Code 2" is represented by 2 fast flashes fol-lowed by a 10-second pause. This sequence will repeat continuallyuntil the fault is cleared.13