7*Assumes both cooler and condenser nozzles on same end ofchiller.†Compressor frame size 2.**Compressor frame size 3.††Compressor frame size 4.***Compressor frame size 5.TABLE 1 NOTES:1. Service access should be provided per American Society ofHeating, Refrigerating, and Air-Conditioning Engineers(ASHRAE) 15, latest edition, National Fire Protection Associa-tion (NFPA) 70, and local safety code.2. Allow at least 3 ft (915 mm) overhead clearance for service rig-ging for frame 2-4 compressor. Overhead clearance for servicerigging frame 5 compressor should be 5 ft (1524 mm).3. Dimensions are approximate. Certified drawings available uponrequest.4. Marine waterboxes may add 6 in. to the width of the machine.See certified drawings for details.5. ‘A’ length dimensions shown are for standard 150 psig designand Victaulic connections. The 300 psig design and/or flangeswill add length. See certified drawings.6. Not all waterbox/pass combinations are available with unit-mounted VFD. Check selection program and Drawing Managerfor availability.7. 19XRV heights can vary depending on the configuration. Check19XRV certified drawings for height information.Table 2 — 19XR Nozzle SizeTable 3 — 19XR Dimensions (Marine Waterbox)*Assumes both cooler and condenser nozzles on same end of chiller.†1 or 3-pass length applies if cooler is a 1 or 3-pass design.NOTES:1. Service access should be provided per American Society of Heating,Refrigerating, and Air-Conditioning Engineers (ASHRAE) 15, latest edi-tion, National Fire Protection Association (NFPA) 70, and local safetycode.2. Allow at least 3 ft (915 mm) overhead clearance for service rigging forframe 2-4 compressor. Overhead clearance for service rigging frame 5compressor should be 5 ft (1524 mm).3. Dimensions are approximate. Certified drawings available upon request.4. Marine waterboxes may add 6 in., to the width of the machine. See certi-fied drawings for details.5. ‘A’ length dimensions shown are for standard 150 psig design and Victau-lic connections. The 300 psig design and/or flanges will add length. Seecertified drawings.6. 19XR,XRV height can vary depending on the configuration. Check 19XR,XRV certified drawings for height information.7. Not all waterbox/pass combinations are available with unit-mounted VFD(variable frequency drive). Check selection program for availability.FRAMESIZENOZZLE SIZE (IN.)(NOMINAL PIPE SIZE)COOLER CONDENSER1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASS1 8 6 6 8 6 62 10 8 6 10 8 63 10 8 6 10 8 64 10 8 6 10 8 65 10 8 6 10 10 86 10 10 8 10 10 87 14 12 10 14 12 128 14 14 12 14 14 12HEAT EXCHANGERSIZEA (LENGTH, MARINE WATERBOX) 19XRB WIDTH19XRVB WIDTH 19XR,XRVC HEIGHT2-PASS* 1 OR 3-PASS†FT-IN. MM FT-IN. MM FT-IN. MM FT-IN. MM10 TO 12 NA NA NA NA NA NA NA NASeeNote 615 TO 17 NA NA NA NA NA NA NA NA20 TO 22 12- 5 1 / 2 3797 14- 1 1 / 4 4299 6- 1 1 / 16 1856 6- 1 1 / 16 185630 TO 32 14- 9 4496 16- 4 3 / 4 4997 6- 1 1 / 16 1856 6- 1 1 / 16 185635 TO 37 16- 5 1 / 2 5017 18- 1 1 / 4 5518 6- 1 1 / 16 1856 6- 1 1 / 16 185640 TO 42 15- 2 3 / 4 4642 16- 8 1 / 4 5086 6- 3 1 / 4 1911 6- 3 1 / 4 191145 TO 47 16-11 1 / 4 5163 18- 4 3 / 4 5607 6- 3 1 / 4 1911 6- 3 1 / 4 191150 TO 54, 5K TO 5R 15- 3 1 / 2 4661 16- 8 1 / 2 5093 6- 8 7 / 8 2054 6- 8 7 / 8 20545A TO 5C 15- 3 1 / 2 4661 16- 8 1 / 2 5093 6- 8 7 / 8 2054 6- 8 7 / 8 205455 TO 59, 5T TO 5Z 17- 0 5182 18- 5 5613 6- 8 7 / 8 2054 6- 8 7 / 8 20545F TO 5H 17- 0 5182 18- 5 5613 6- 8 7 / 8 2054 6- 8 7 / 8 205460 TO 64, 6K TO 6R 15- 4 1 / 8 4677 16- 8 3 / 4 5099 6-113 / 4 2127 6- 11 3 / 4 212765 TO 69, 6T TO 6Z 17- 0 5 / 8 5197 18- 5 1 / 4 5620 6-113 / 4 2127 6- 11 3 / 4 212770 TO 74, 7K TO 7R 18- 3 5 / 8 5579 19- 9 3 / 4 6039 8- 8 1 / 8 2645 9- 6 3 / 8 290575 TO 79, 7T TO 7Z 20- 3 5 / 8 6188 21- 9 3 / 4 6649 8- 8 1 / 8 2645 9- 6 3 / 8 290580 TO 84, 8K TO 8R 18- 4 5583 19-101 / 2 6058 9- 5 5 / 8 2886 10- 5 317585 TO 87, 8T TO 8Z 20- 4 6198 21-101 / 2 6668 9- 5 5 / 8 2886 10- 5 3175