38Table 14 — 30RAP Electrical Data — Dual Point, Low Sound AeroAcoustic™ Fan, No Hydronic PackageLEGENDNOTES:1. Units are suitable for use on electrical systems where voltage supplied tothe unit terminals is not below or above the listed minimum and maximumlimits. Maximum allowable phase imbalance is: voltage, 2%; amps 10%.2. All units/modules have dual point primary power connection. (Each unit/module requires its own power supply.) Main power must be supplied froma field-supplied disconnect.3. Cooler heater is wired into the control circuit so it is always operable aslong as the power supply disconnect and heater safety device are on.4. Power draw control circuits include both crankcase heaters (sizes 070-150 only) and cooler heaters (where used). Each compressor on sizes070-090 has a crankcase heater which draws 90 watts of power, whileeach compressor on sizes 100-150 has a crankcase heater which draws56 watts of power.UNIT30RAPUNIT VOLTAGE CIRCUIT 1 CIRCUIT 2V-Hz(3 Ph)Supplied MCA MOCP ICF Rec FuseSize MCA MOCP ICF Rec FuseSizeMin Max070208/230-3-60 187 254 155.6 200 425.8 175 181.4 225 451.6 200380-3-60 342 418 96.0 125 249.5 110 110.5 125 264.0 125380/415-3-50 342 440 75.0 100 220.4 90 87.4 110 232.8 100460-3-60 414 506 75.0 100 220.4 90 87.4 110 232.8 100575-3-60 518 632 65.3 80 167.7 80 77.0 100 179.4 90080208/230-3-60 187 254 202.7 250 438.6 225 181.4 225 451.6 200380-3-60 342 418 110.8 125 216.2 125 110.5 125 264.0 125380/415-3-50 342 440 92.5 110 213.6 100 87.4 110 232.8 100460-3-60 414 506 92.5 110 213.6 100 87.4 110 232.8 100575-3-60 518 632 79.1 90 163.2 90 77.0 100 179.4 90090208/230-3-60 187 254 217.4 250 487.6 250 181.4 225 451.6 200380-3-60 342 418 133.9 150 287.4 150 110.5 125 264.0 125380/415-3-50 342 440 104.8 125 250.2 125 87.4 110 232.8 100460-3-60 414 506 104.8 125 250.2 125 87.4 110 232.8 100575-3-60 518 632 91.4 110 193.8 100 77.0 100 179.4 90100208/230-3-60 187 254 234.8 300 677.0 300 243.8 300 635.0 300380-3-60 342 418 127.3 175 380.7 150 124.8 150 336.8 150380/415-3-50 342 440 105.0 150 313.0 125 106.3 125 280.4 125460-3-60 414 506 105.0 150 313.0 125 106.3 125 280.4 125575-3-60 518 632 85.4 125 253.0 100 85.2 110 227.4 100115208/230-3-60 187 254 291.8 350 683.0 350 243.8 300 635.0 300380-3-60 342 418 156.0 175 368.0 175 124.8 150 336.8 150380/415-3-50 342 440 129.5 150 303.6 150 106.3 125 280.4 125460-3-60 414 506 129.5 150 303.6 150 106.3 125 280.4 125575-3-60 518 632 104.4 125 246.6 125 85.2 110 227.4 100130208/230-3-60 187 254 297.8 350 689.0 350 306.2 400 748.4 350380-3-60 342 418 159.9 175 371.9 175 160.2 200 413.6 175380/415-3-50 342 440 132.4 150 306.5 150 135.2 175 343.2 150460-3-60 414 506 132.4 150 306.5 150 135.2 175 343.2 150575-3-60 518 632 106.8 125 249.0 125 110.2 125 277.8 125150208/230-3-60 187 254 366.2 450 808.4 400 306.2 400 748.4 350380-3-60 342 418 199.2 225 452.6 225 160.2 200 413.6 175380/415-3-50 342 440 164.2 200 372.2 175 135.2 175 343.2 150460-3-60 414 506 164.2 200 372.2 175 135.2 175 343.2 150575-3-60 518 632 134.2 150 301.8 150 110.2 125 277.8 125ICF — Instantaneous Current FlowMCA — Minimum Circuit AmpsMOCP — Maximum Overcurrent Protection
PreviousNext |