TABLE V—AIRFLOW (CFM) AT INDICATEDTEMPERATURE RISE AND RATED INPUT585A/YAC, 585A/YACR,& 586A/YACX SizeHeatingInput BtuhTemperature Rise (®F) |45 50 55 60 65 70 75018050 50,000 770 695 630 580 535 495 465024055 55,000 850 765 695 635 545 510024080, 030080,& 03608080,000 1235 1110 1010 925 855 795 740036100 & 042100 100,000 1545 1390 1265! 1155 1070 990 925036125, 042125,048125, & 060125125,000 1930 1735 1580 1445 1335 1240 1155048150 & 060150 i 150,000 iEg&] IRgIil|TABLE VI—AIR DELIVERY (CFM) AT INDICATED EXTERNAL STATIC PRESSUREAND VOLTAGE WITH FIELD-SUPPLIED FILTER*585A/YAC, 585A/YACR, & 586A/YACXSizeMotor SpeedTapt0.1 0.2 0.3 0.4 0.5 0.6208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V018050 Heating-L 770 740 690 700 660 650 620 590 580 510 510Cooling-L 750 720 680 680 600 550 — —024055 Heating-L 710 740 690 700 660 620 590 580 510 510Cooling-H 870 ■IggQII 790 ■SB {^■■1024080 Heating-M 900 970 860 820 880 770 830 - 7701Cooling-L 780 860 740 830 700 ■■■ ■^■1030080 Heating-M 900 970 860 770 830 — 770Cooling-H 1170 1200 1120 1150 1060 1090 990 1030 920 950 —1 5►85A/YAC & 585A/YACR I036080 Heating-L ■IKiM 970 1060 910 1010 870 940 820Cooling-H 1430 1440 1370 1370 MjcTiKM 1170 1140 — —036100 Heating-L ■iclsIiM 1240 1310 1190 ■sjsB 1140 1200 1070 1110Cooling-L 1310 1270 1310 1220 1280 1160 1230 1100 1160 — 1050036125 Heating-H 1510 1560 1450 1500 1390 1360 1230 1280Cooling-L 1270 1310 1220 mFssm 1100 1160 — 1050042100 Heating-L 1330 1390 1290 1350 mmm msEsm 1140 1200 1070 1110Cooling-H 1540 1590 1490 1530 1430 ■ETiIiM 1280 1320 — 1240042125 Heating-H ■EMiM 1500 1390 1430 1320 1360 1230 1280Cooling-H 1490 1530 1430 1470 1360 1400 1280 1320 — 1240048125 Heating-L 1440 1410 1400 1360 1360 1310 1310 1250 1250 1170 1160Cooling-H 1620 1660 1560 1590 1480 1510 — — — —048150 Heating-H 2120 2160 2050 2090 1970 2020 1880 1930 1790 1830 1660 1690Cooling-M »l;gM WBSEM ■miM 1760 1610 1630 — —060125 Heating-L — — mimm AisliM 1440 1540 1330 1450Cooling-H 2080 2120 2000 2050 1920 1970 1830 — 1750 — —060150 Heating-M 1910 2000 1870 1950 1820 1890 1750 1810 1670 1710 1530 1540Cooling-H 1870 — 1750 — —*Data includes a deduction of 0.08 in. wc for fieldrsupplied filter. For units operating attHeating CFM values are with dry coil. Cooling CFM values are with wet coil.—Indicates portions of the table that are not within the recommended operating range.460 volts, use CFM values shown for 230 volts.TABLE VII—AIR DELIVERY (CFM) AT INDICATED EXTERNAL STATIC PRESSUREAND VOLTAGE WITH FIELD-SUPPLIED FILTER*586A/YACXt 1SizeApplication—Motor SpeedTapi:External Static Pressure—Inches wc I0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V036080 Heating-L 1360 1320 1280 1320 1210 1250 1130 1010 1040 900 930 740 760Cooling-H 1660 1710 1580 1630 1470 1520 1370 1410 1240 1280 1100 1130036100 Heating-L 1550 ■IgtllM ■MUM 1,560 1510 1410 1450 1340 1380 1240 1280 1120 1150 740 760Cooling-L 1530 1540 1440 1480 1370 1410 1290 1330 1180 1220 — 1060 —036125 Heating-M 1870 1790 1850 1720 1770 1630 1680 1530 1580 1470 1290 1330 — —Cooling-L 1530 ■gQI 1540 1440 1480 1380 1420 1330 1180 1220 — 1060 — —042100 Heating-L 1550 1600 1510 1560 1460 1510 1400 1450 1340 1380 1240 1280 1120 1150 — —Cooling-M 1850 1890 1770 1810 1700 1730 1610 1640 1500 1530 1380 1410 1230 1250 — —042125 Heating-M 1870 1930 1790 1850 1720 1770 1630 1680 1530 1580 1430 1470 1290 1330 — —Cooling-M 1850 1890 1770 1810 1700 1730 1610 1640 1500 1530 1380 1410 1230 1350 — —048125 Heating-M 1870 1930 1790 1850 1720 1770 1630 1680 1530 1580 ■E^ 1470 1290 1330 — —Cooling-H 2090 2130 1990 2030 1890 1930 1780 1820 1670 1700 1540 1570 — 1420 — —048150 Heating-H 2240 2290 2170 2210 2070 2110 1960 2000 1840 1880 1700 1730 1510 1540 — —Cooling-H 2200 2240 2110 2150 2000 2040 1890 1930 1750 1790 1590 1620 _ — — —060125 Heating-L 1620 1650 1560 1590 1490 1520 1420 ‘ 1450 1330 1360 1230 1260 — — — —Cooling-H 2410 2460 2320 2370 2230 2280 2140 2180 2020 2060 1890 1930 — 1770 — —060150 Heating-M 2080 2120 1990 2030 1890 1930 1790 1830 1700 1730 1590 1620 1470 1500 — —CooIing-H 2410 2460 2320 2370 2230 2280 2140 2180 2020 2060 1890 1930 mnsm*Data includes a deduction of 0.08 in. wc for field-supplied filter. For units operating at 460 volts, use CFM values shown for 230 volts.tAir delivery data in this table also applies to the 585A/YAC and 585A/YACR with optional field-installed high-static blower installed.tHeating CFM values are with dry coil. Cooling CFM values are with wet coil.—Indicates portions of the table that are not within the recommended operating range.-10-