14A08060A08057Edge Thermidistat Models TP---PRH ---01 & TP---NRH ---01w/ Fan Coil & 2 ---Stage Air ConditionerEdge Thermidistat Models TP---PRH ---01 & TP---NRH ---01w/ Furnace & 2 ---Stage Air ConditionerRVS/Heat Stage 2 O/W2/BHeat Stage 1 W/W1Compressor Low Y1Compressor High Y/Y2Fan G24VAC Hot Heating Rh24VAC Hot Cooling RcDry Contact 1 D1Dry Contact 2 D224VAC Common CHumidify HUMOutdoor Air Temp OATRemote Room Sensor RRSOAT/RRS ReturnSRTNSRTNOutdoor SensorHumidifier SolenoidValveRemote RoomSensorOY1W1GW2CY2RY1Y/Y2RCDHREMOVE J2JUMPER FORHEAT STAGINGREMOVE J1 FORDEHUMIDIFYMODESTwo-StageAir ConditionerThermidistatVariable SpeedFan CoilRVS/Heat Stage 2 O/W2/B W2Heat Stage 1 W/W1 W1Compressor Low Y1 Y1 Y1Compressor High Y/Y2 Y/Y2 Y2Fan G G24VAC Hot Heating Rh R R24VAC Hot Cooling RcDry Contact 1 D1Dry Contact 2 D2 DHUM24VAC Common C COM CHumidify HUMOutdoor Air Temp OATRemote Room Sensor RRSOAT/RRS ReturnSRTNSRTNOutdoor SensorHumidifier SolenoidValveRemote RoomSensorTHERMIDISTAT VARIABLE SPEEDFURNACETWO-STAGEAIR CONDITIONERA09338Thermidistat Model TP---PRH ---01 or TP---NRH ---01w/ VS Furnace & 2 ---Stage Air ConditionerVariable SpeedFurnaceThermidistat 2-StageAir ConditionerHeat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1Cool Stage 1 Y1 / W2 Y1Cool Stage 2 Y/Y2 Y/Y2 Y/Y2Fan G G24VAC Hot Heating Rh R R24VAC Hot Cooling RcDry Contact 1 D1Dry Contact 2 D2 DHUM24VAC Common C COM CHumidify HUMOutdoor Air Temp OATRemote Room Sensor RRSOAT/RRS Com SRTNOutdoor Sensor *Humidifier SolenoidValve *Remote RoomSensor ** Indicates connection may not be required / available.LEGEND24 VOLT FACTORY WIRING24 VOLT FIELD WIRINGFIELD SPLICE CONNECTIONRELAY SPDT, PILOT DUTY24-V COIL (HN61KK324)OR EQUIVALENTHUMIDISTAT, OPENS ONHUMIDITY RISE (HL38MG026)AIRFLOW SELECTORR1HAFSA02005Fig. 10 -- Thermidistat Wiring with 2--Stage Puron refrigerant Air Conditioner24ANA