14Table 5 — Program Parameters for the Operating ModeLEGENDPARAMETERS DESCRIPTION MODE 1 MODE 2 MODE 4P01 Line Voltage: 01 = low line, 02 = high line 01 02 02P02 Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01P03 Startup mode: flying restart 06 06 06P04 Stop mode: coast to stop 01 01 01P05 Standard Speed source: 01 = keypad, 04 = 4-20mA (NO PI), 05 = R22 or R410A,06 = R134a 05 05 05P06 TB-14 output: 01 = none 01 01 01P08 TB-30 output: 01 = none 01 01 01P09 TB-31 Output: 01 = none 01 01 01P10 TB-13A function sel: 01 = none 01 01 01P11 TB-13B function sel: 01 = none 01 01 01P12 TB-13C function sel: 01 = none 01 01 01P13 TB-15 output: 01 = none 01 01 01P14 Control: 01 = Terminal strip 01 01 01P15 Serial link: 02 = enabled 9600,8,N,2 with timer 02 02 02P16 Units editing: 02 = whole units 02 02 02P17 Rotation: 01 = forward only, 03 = reverse only 01 01 01P19 Acceleration time: 20 sec 20 20 20P20 Deceleration time: 10 sec 10 10 10P21 DC brake time: 0 0 0 0P22 DC BRAKE VOLTAGE 0% 0 0 0P23 Min freq = 8 Hz ~ 100 – 160 rpm 8 8 8P24 Max freq 60 60 50P25 Current limit: (%) 125 110 110P26 Motor overload: 100 100 100 100P27 Base freq: 60 or 50 Hz 60 60 50P28 Fixed boost: 0.5% at low frequencies 0.5 0.5 0.5P29 Accel boost: 0% 0 0 0P30 Slip compensation: 0% 0 0 0P31 Preset spd #1: speed if loss of control signal 57 57 47P32 Preset spd #2: 0 0 0 0P33 Preset spd #3: 0 0 0 0P34 Preset spd 4 default — R22 setpoint. TB12-2 open 24.0 24.0 24.0P35 Preset spd 5 default — R134a setpoint. TB12-2 closed 12.6 12.6 12.6P36 Preset spd 6 default 0 0 0P37 Preset spd 7 default 0 0 0P38 Skip bandwidth 0 0 0P39 Speed scaling 0 0 0P40 Frequency scaling 50 or 60 Hz 60 60 50P41 Load scaling: default (not used so NA) 200 200 200P42 Accel/decel #2: default (not used so NA) 60 60 60P43 Serial address 1 1 1P44 Password:111 111 111 111P45 Speed at min signal: 8 Hz; used when PID mode is disabled and 4-20 mA input isat 4 mA 8 8 8P46 Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20 mA input isat 20 mA 60 60 50P47 Clear history? 01 = maintain. (set to 02 to clear) 01 01 01P48 Program selection: Program 1 – 12 01 02 04P61 PI Mode: 05 = reverse, 0-5V, 01 = no PID 05 05 05P62 Min feedback = 0 (0V *10) 0 0 0P63 Max feedback = 50 (5V * 10) 50 50 50P64 Proportional gain = 3.5% 3.5 3.5 3.5P65 Integral gain = .2 .2 .2 .2P66 PI accel/decel (setpoint change filter) = 10 10 10 10P67 Min alarm 0 0 0P68 Max alarm 0 0 0NA — Not ApplicablePI — Proportional IntegralPID — Proportional Integral Derivative