7Electrical data* Permissible limits of the voltage range at which unit will operate satisfactorily.† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathedcable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated(non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used,consult applicable tables of the NEC (ANSI/NFPA 70).‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.** Time-delay fuse.FLA — Full Load AmpsLRA — Locked Rotor ArmsMCA — Minimum Circuit AmpsRLA — Rated Load AmpsNOTE: Control circuit is 24-v on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.A-weighted sound power (dBA)NOTE: Tested in accordance with ARI standard 270.95. (Not listed with ARI.)UNIT SIZE-SERIES V/PHOPER VOLTS* COMPR FANFLA MCA60°CMINWIRESIZE†75°CMINWIRESIZE†60°CMAXLENGTH(Ft)‡75°CMAXLENGTH(Ft)‡MAXFUSE**CKT BKRAMPSMax Min LRA RLA024-34208/230/1 253 18760.0 12.8 0.8 16.8 14 14 46 44 25030-33 72.5 14.7 0.8 19.2 14 14 41 39 30036-33 83.0 15.4 1.1 20.4 12 12 62 59 30042-33 105.0 18.6 1.1 24.4 10 10 81 77 40048-31 109.0 20.5 1.1 26.7 10 10 74 70 40060-30 145.0 26.9 1.4 35.0 8 8 89 84 60UNITSIZE-SERIES STANDARDRATINGTYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)125 250 500 1000 2000 4000 8000024-34 71 54.5 64.0 64.5 63.5 61.0 56.0 48.0030-33 70 55.5 60.5 63.0 65.0 63.0 58.0 51.0036-33 72 56.5 64.0 65.0 67.0 63.0 58.5 50.0042-33 73 58.5 66.5 66.0 66.5 64.5 59.0 50.5048-31 76 57.0 66.0 69.0 70.0 66.0 58.0 53.0060-30 78 56.5 67.0 71.5 70.5 70.5 60.5 53.0