SiUS121502E Function of CTXS, FTXS, CDXS, FDXS, FVXS SeriesFunction and Control 451.11 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operatedby increasing the indoor fan rotating speed and the compressor frequency.Detail When POWERFUL button is pressed, the fan speed and target temperature are converted to thefollowing states for 20 minutes.A = 50 ~ 90 rpm (depending on the model)Ex: POWERFUL operation in coolingNote: POWERFUL operation cannot be used together with ECONO or COMFORT AIRFLOW operation.Operation mode Fan speed Target temperatureCOOL H tap + A rpm 18°C (64.4°F)DRY Dry rotating speed + A rpm Lowered by 2 ~ 2.5°C(3.6 ~ 4.5°F)HEAT H tap + A rpm 30 ~ 31.5°C (86 ~ 88.7°F)FAN H tap + A rpm —AUTO Same as cooling / heating inPOWERFUL operation The target temperature iskept unchanged.(R19193)Target temp.Fan A rpm18˚C (64.4˚F)H tapSet tap20 minutesIt should be the lower limit ofcooling temperature.It counts 20 minutes alsoin the remote controller.POWERFULONPOWERFULOFFEnding condition:1. After the lapse of 20 minutes.2. Operation OFF3. POWERFUL operation is OFF.