nEnglish 8Refrigerant Piping Work5. Refilling the refrigerantCheck the type of refrigerant to be used on the machine nameplate.Precautions when adding R410AFill from the gas pipe in liquid form.It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphonattached” displayed on it.)2) Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.6. Charging with refrigerant1) If the total length of piping for all rooms exceeds the figure listed below, additionally charge with 20g of refrigerant (R410A)for each additional meter of piping.NOTE:National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriateofficial national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is suppliedwith the unit.Sticking instructions are illustrated on the backside of that label.CAUTIONEven though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a longperiod of time.Outdoor capacity class 3MXS40, 3MXS52, 3AMX52Total length of piping for all rooms 30mFilling a cylinder with an attached siphonStand the cylinder upright when filling.There is a siphon pipe inside, so the cylinderneed not be upside-down to fill with liquid.Filling other cylindersTurn the cylinder upside-downwhen filling.356214Please fill in with indelible ink, |