4 InstallationInstallation manual7EPGA11~16DAV3Daikin Altherma – Low temperature split4P556065-1 – 2018.10≥150620350(345-355)a(mm)261.56× M12a Make sure not to cover the drain holes.In any case, make sure the unit is positioned at least 100 mm abovethe maximum expected level of snow.4.2.2 To install the outdoor unit6× M124.2.3 To provide drainageMake sure that condensate can be evacuated properly. When theunit is in cooling mode, condensate may also form in the hydro part.When providing drainage, therefore make sure to cover the entireunit.NOTICEIf the unit is installed in a cold climate, take adequatemeasures so that the evacuated condensate CANNOTfreeze.Drain holes (dimensions in mm)160 620 261.5 1191612602852793455954162623871 CDEDDDDABA Discharge sideB Distance between anchor pointsC Bottom frameD Drain holesE Knockout hole for snowNOTICEIf drain holes of the outdoor unit are covered by a mountingbase or by floor surface, raise the unit to provide a freespace of more than 150 mm under the outdoor unit.≥150 mm4.2.4 To fix the fluorinated greenhouse gaseslabel1 Fill in the label as follows:RXXXdContains fluorinated greenhouse gaseskgtCO2eqGWP × kg1000 =GWP: XXXabca If a multilingual fluorinated greenhouse gases label isdelivered with the unit (see accessories), peel off theapplicable language and stick it on top of a.b Total refrigerant chargec Greenhouse gas emissions of the total refrigerant chargeexpressed as tonnes CO2 equivalentd GWP = Global warming potentialNOTICEIn Europe, the greenhouse gas emissions of the totalrefrigerant charge in the system (expressed as tonnes CO2equivalent) is used to determine the maintenance intervals.Follow the applicable legislation.Formula to calculate the greenhouse gas emissions:GWP value of the refrigerant × Total refrigerant charge [inkg] / 10002 Fix the label on the inside of the outdoor unit near the gas andliquid stop valves.4.2.5 To prevent the outdoor unit from fallingoverIn case the unit is installed in places where strong wind can tilt theunit, take following measure:1 Prepare 2 cables as indicated in the following illustration (fieldsupply).2 Place the 2 cables over the outdoor unit.3 Insert a rubber sheet between the cables and the outdoor unitto prevent the cables from scratching the paint (field supply).4 Attach the ends of the cables and tighten them.