• Daikin Altherma High Temperature • Outdoor units • ERRQ-AAY1• Heating • Daikin Altherma242 Specifications22Refrigerant Type R-410ACharge kg 4.5 4.5 4.5Control Expansion valve(electronic type)Nr of Circuits 1 1 1Refrigerant Oil Type Daphne FVC68DCharged Volume l 1.5 1.5 1.5Piping connections Liquid (OD) Quantity 1 1 1Type Flare connectionDiameter (OD) mm 9,52Gas Quantity 1 1 1Type Flare connectionDiameter (OD) mm 15,9Drain Quantity 3 3 3Diameter (OD) mm 26x3Piping Length Minimum m 3 3 3Maximum m 50 50 50Equivalent m 63 63 63Chargeless m 10 10 10Additional Refrigerant Charge kg/m see installation manualInstallation heightdifferenceMaximum m 30 30 30Heat Insulation Both liquid and gas pipesDefrost Method Reverse cycleDefrost Control Sensor for outdoor heat exchanger temperatureCapacity Control Method Inverter controlledSafety Devices High pressure switchFan motor thermal protectorInverter overload protectorPC board fuseStandard Accessories Item Installation manualQuantity 1 1 1High pressure side Design pressure bar 40 40 40Notes See operation range drawing2-3 Electrical Specifications ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1Power Supply Name Y1Phase 3~Frequency Hz 50 50 50Voltage V 380-415Voltage range Minimum V 342Maximum V 440Current Maximum runningCurrentHeating A 13,5Recomended fuses A 16 16 16Wiring connections For Power Supply Quantity 4GRemark Select diameter and type according to national and local regulationsFor connection withindoorQuantity 2 2 2Remark F1+F2Power Supply Intake Both indoor and outdoor unit2-2 Technical Specifications ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1