ESIE15-11A | Part 3. Field settings 6. General indoor units23/09/16 Page 41VRV4 indoor units6. General indoor unitsThese settings are applicable to most of the indoor units.10 /200 Filter contamination (time between 2filter cleaning display indications)01 light Ultra-long life Filter: +/-10.000 hrsLong-life filter +/-2.500 hrsStandard filter +/-200 hrs02 heavy Ultra-long life Filter: +/-5.000 hrsLong-life filter +/-1.250 hrsStandard filter +/-100 hrs1 Long life filter type 01 long life filter Filterclass G102 super long life filter(option)Filter type F6 high efficiency 64 forFXCQ-FXUQ-FXFQ-FXZQ-FXKQ-FXSQ-FXDQ-FXFQ-FXMQFilter type F7 for VAM (additional filter)Filter type F8 very high efficiency 90for FXCQ-FXFQ-FXSQ-FXMQ04 oil guard filter for installations in greasy environment2 Indoor thermostat sensor selection(no effect when used in conjunctionwith presence sensor BRYQ)01 Use both the unit sensor(or remote sensor ifinstalled) AND the remotecontroller sensor.Note: If setting 10-6-02 + 10-2-01 or10-2-02 or 10-2-03 are set at thesame time, then setting 10-2-01,10-2-02 or 10-2-03 have priority.Note: If setting 10-6-01 + 10-2-01 or10-2-02 or 10-2-03 are set at thesame time, then setting for group con-nection, 10-6-01 has priority and forindividual connection, 10-2-01,10-2-02 or 10-2-03 have priority.02 Use return air sensor only(or remote sensor ifinstalled).Note: If setting 10-6-02 + 10-2-01 or10-2-02 or 10-2-03 are set at thesame time, then setting 10-2-01,10-2-02 or 10-2-03 have priority.Note: If setting 10-6-01 + 10-2-01 or10-2-02 or 10-2-03 are set at thesame time, then setting for group con-nection, 10-6-01 has priority and forindividual connection, 10-2-01,10-2-02 or 10-2-03 have priority.03 Use remote controller sen-sor only.Note: If setting 10-6-02 + 10-2-01 or10-2-02 or 10-2-03 are set at thesame time, then setting 10-2-01,10-2-02 or 10-2-03 have priority.Note: If setting 10-6-01 + 10-2-01 or10-2-02 or 10-2-03 are set at thesame time, then setting for group con-nection, 10-6-01 has priority and forindividual connection, 10-2-01,10-2-02 or 10-2-03 have priority.3 Filter sign display 01 Display02 Do not display5 Remote controller thermistor visible bycentral control device in group wiringP1P201 no02 yes6 Air thermistor selection in group wiringP1P201 return air thermistor (indi-vidual units)02 Thermistor designated byfieldsetting 20-27 Absence delay detecting time (pres-ence sensor)01 30 minutes02 60 minutes8 Compensation air sensor heating 01 add 2°C to measurementair sensor02 measurement air sensor