EDUS39-800-F8 InstallationBSVQ-P 11• Be very careful about product transportation.Some products use PP bands for packaging. Do not use any PP bands for a means of transportation.It is dangerous.• Make sure to provide for adequate measures in order to prevent that the outside unit be used as ashelter by small animals.Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instructthe customer to keep the area around the unit clean.NOTE• Install the indoor and outside units, power supply wiring and connecting wires at least 3.5ft. awayfrom televisions or radios in order to prevent image interference or noise.(Depending on the radio waves, a distance of 3.5ft. may not be sufficient enough to eliminate the noise.)• Remote controller (wireless kit) transmitting distance can result shorter than expected in roomswith electronic fluorescent lamps. (inverter or rapid start types)Install the indoor unit as far away from fluorescent lamps as possible.• This unit is a class A product.In a domestic environment this product may cause radio interference in which case the user may berequired to take adequate measures.• Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done inaccordance with the relevant local and national regulations.NOTEThe refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.A. Clean and dryForeign materials (including mineral oils such as SUNISO oil or moisture) should be prevented fromgetting mixed into the system.B. TightR410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce theearth’s protection against harmful ultraviolet radiation.R410A can contribute slightly to the greenhouse effect if it is released. Therefore we should take spe-cial attention to check the tightness of the installation.Read the chapter “Refrigerant piping work” carefully and follow these procedures correctly.2. BEFORE INSTALLATION2-1 CAUTION CONCERNING NEW REFRIGERANT SERIES• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. (Ifthe refrigerant is charged in a state of gas, its composition changes and the system will not work properly.)The indoor/outside unit is for R410A. See the catalog for indoor/outside unit models which can be connected.(Normal operation is not possible when connected to other units.)2-2 PRECAUTIONS• Hold the unit by the Hanging brackets (4 points) when opening the box and moving it, and do not lift it hold-ing on to any other part especially the refrigerant piping.• About installation of outside and indoor unit, refer to the installation manual provided with the outside andthe indoor unit.• This unit, both indoor and outside, is suitable for installation in a commercial and light industrial environment.If installed as a household appliance it could cause electromagnetic interference.