14 Technical dataInstaller reference guide79EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3Daikin Altherma low temperature monobloc4P538847-1 – 2018.0514 Technical dataA subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data isavailable on the Daikin extranet (authentication required).14.1 Service space: Outdoor unitSingle unitA~E a b* b† c d He eB eDHB HD HU(mm)A, B, C — ≥500 ≥250 ≥100A, B, C, E ———≥500 ≥250 ≥150 ≥1000 ≤500≤500D ≥500≥500D, E ≥1000 ≤500B, D ≥250 ≥500B, D, E ≥250≥250≥400≥400≥400≥400≥400≥1000≥150≥150≥150≥150≥150≥150≥150≥1000≥1000 ≥1000 ≤500HDUHDU&&HB>HUHD>HUHBU*,†ab*,†cdeeBeDABCDEHBHUHDA,C Left side and right side obstacles (walls/baffle plates)B Suction side obstacle (wall/baffle plate)D Discharge side obstacle (wall/baffle plate)E Top side obstacle (roof)a,b,c,d,e Minimum service space between the unit and obstacles A, B, C, D and E* If shut-off valves are NOT installed on the unit† If shut-off valves are installed on the uniteB Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle BeD Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle DHU Height of the unit including the installation structureHB,HD Height of obstacles B and DH Height of installation structure below the unitINFORMATIONIf shut-off valves are installed on the unit, provide aminimum space of 400 mm at the air inlet side. If shut‑offvalves are NOT installed on the unit, provide a minimumspace of 250 mm.