ERQ100~140A7V1BInverter condensing unit4PW51321-1Installation manual10See figure 6.To avoid compressor breakdown. Do not charge the refrigerantmore than the specified amount.■ This outdoor unit is factory charged with refrigerant anddepending on pipe sizes and pipe lengths some systems requireadditional charging of refrigerant. See "How to calculate theadditional refrigerant to be charged" on page 10.■ In case re-charge is required, refer to the nameplate of the unit.The nameplate states the type of refrigerant and necessaryamount.Installation limitationsHow to calculate the additional refrigerant to be chargedAdditional refrigerant to be charged R (kg)R should be rounded off in units of 0.1 kgR=(Total length (m) of liquid piping size at Ø9.5)x0.054Determine the weight of refrigerant to be charged additionallyreferring to the item "Additional refrigerant charge" in "How tocalculate the additional refrigerant to be charged" on page 10 and fillin the amount in the "Additional refrigerant charge label" attached tothe unit.Precautions when adding R410ABe sure to charge the specified amount of refrigerant in liquid state tothe liquid pipe.Since this refrigerant is a mixed refrigerant, adding it in gas form maycause the refrigerant composition to change, preventing normaloperation.■ Before charging, check whether the refrigerant cylinder isequipped with a siphon tube or not.10.1. Important information regarding the refrigerantusedThis product contains fluorinated greenhouse gases covered by theKyoto Protocol. Do not vent gases into the atmosphere.Refrigerant type: R410AGWP (1) value: 1975(1) GWP = global warming potentialPlease fill in with indelible ink,■ ➀ the factory refrigerant charge of the product,■ ➁ the additional refrigerant amount charged in the field and■ ➀+➁ the total refrigerant chargeon the fluorinated greenhouse gases label supplied with the product.The filled out label must be adhered on the inside of the product andin the proximity of the product charging port (e.g. on the inside of theservice cover).1 Pressure reducing valve2 Nitrogen3 Tank4 Siphon system5 Measuring instrument6 Vacuum pomp7 Valve A8 Gas line stop valve9 Outdoor unit10 Liquid line stop valve11 Air handling unit12 Stop valve service port13 Charge hose1 Outdoor unit2 Valve kit3 Air handling unitMax (m) Min (m)L1 50 5L2 5 —A –5 / +5(*)(*) Below or above the outdoor unit.—B –35 / +35(*) —L1L2AB123Charge the liquidrefrigerant with the cylinderin upright position.Charge the liquidrefrigerant with the cylinderin up-side-down position.NOTE National implementation of EU regulation on certainfluorinated greenhouse gases may require to providethe appropriate official national language on the unit.Therefore, an additional multilingual fluorinatedgreenhouse gases label is supplied with the unit.Sticking instructions are illustrated on the backside ofthat label.356214 1 factory refrigerant chargeof the product:see unit name plate2 additional refrigerantamount charged in thefield3 total refrigerant charge4 Contains fluorinatedgreenhouse gasescovered by the KyotoProtocol5 outdoor unit6 refrigerant cylinder andmanifold for charging