Installation and operation manual39 EWAQ016~064BAW + EWYQ016~064BAWPackaged air-cooled water chiller4PW70082-1C – 2013.076.1.1. Field settings tableFirstcodeSecondcode Setting nameInstaller setting at variance with default valueDefaultvalue Range Step UnitDate Value Date Value0 Remote control setup00 User permission level 2 2~3 1 —01 Room temperature compensation value 0 –5~5 0.5 °C02 Not applicable. Do not change the default value. 1 — — —03 Status: space heating schedule timer modeMethod 1=1 / Method 2=0 1 (ON) 0/1 — —04 Status: space cooling schedule timer modeMethod 1=1 / Method 2=0 1 (ON) 0/1 — —1 Settings are not applicable00 Not applicable. Do not change the default value. 1 — — —01 Not applicable. Do not change the default value. 1:00 — — —02 Not applicable. Do not change the default value. 0 — — —03 Not applicable. Do not change the default value. 15:00 — — —2 Automatic setback function00 Status: setback operation 1 (ON) 0/1 — —01 Setback operation start time 23:00 0:00~23:00 1:00 hour02 Setback operation stop time 5:00 0:00~23:00 1:00 hour3 Weather dependent set point00 Low ambient temperature (Lo_A) –10 –20~5 1 °C01 High ambient temperature (Hi_A) 15 10~20 1 °C02 Set point at low ambient temperature (Lo_Ti) 40 25~80 1 °C03 Set point at high ambient temperature (Hi_Ti) 25 25~80 1 °C4 Settings are not applicable00 Not applicable. Do not change the default value. 1 — — —01 Not applicable. Do not change the default value. Fri — — —02 Not applicable. Do not change the default value. 23:00 — — —5 Automatic setback and disinfection set point00 Not applicable. Do not change the default value. 70 — — —01 Not applicable. Do not change the default value. 10 — — —02 Leaving water setback temperature 5 0~10 1 °C03 Room setback temperature 18 17~23 1 °C04 Not applicable. Do not change the default value. 1 — — —6 Option setup01 Optional room thermostat installed 0 0~2 — —03 Negative leaving water temperature setting 0 0~–10 –1 °C7 Option setup00 Forced pump operation 1 (ON) 0/1 — —8 Option setup00 Remote controller temperature control 0 (OFF) 0/1 — —01 Not applicable. Do not change the default value. 1 — — —03 Not applicable. Do not change the default value. 1 — — —04 Status: freeze-up prevention 0 0~2 1 —9 Automatic temperature compensation00 Leaving water temperature compensation value(heating) 0 –2~2 0.2 °C01 Leaving water thermistor auto corrective function 1 (ON) 0/1 1 —02 Not applicable. Do not change the default value. 0 — — —03 Leaving water temperature compensation value(cooling) 0 –2~2 0.2 °C04 Not applicable. Do not change the default value. 0 — — —