Prior to start - uPwww.DaikinApplied.com 25 IM 1049-9Unit Size 060 (380/50/3, 460/60/3,575/60/3)The fan motor on unit size 060 for voltages 380/50/3,460/60/3 and 575/60/3 (Figure 29) have a five-positionterminal block and are factory wired for high speed. Lowspeed can be achieved by interchanging black terminal(3) with red terminal (5) and the black and blue terminals(3 & 4) receive a jumper as shown in Figure 30.Figure 29: Size 060 (380/50/3, 460/60/3, 575/60/3 factorywired for high speed1 (YEL)2 (BRN)3 (BLK)4 (BLU)5 (RED)LINELINEHIGH SPEEDFACTORY WIREDGRNCAPACITORFAN MOTORFigure 30: Size 060 (380/50/3, 460/60/3, 575/60/3 low speed1 (YEL)2 (BRN)3 (BLK)4 (BLU)5 (RED)LINELINELOW SPEEDJUMPER LEADGRNCAPACITORFAN MOTORUnit Size 070 (208-230/60/3)The fan motor on unit size 070 in voltage 208-230/60/3has a four-position terminal block and is factory wired forhigh speed (Figure 31). Low speed can be achieved byinterchanging black terminal (3) with red terminal (4).Figure 31: Sizes 070 (208-230/60/3)1 (YEL)2 (BRN)3 (BLK)4 (RED)LOWLINEHIGHFACTORYWIREDGR / YE CAPACITORFAN MOTORUnit Size 070 (460/60/3, 575/60/3)The fan motor on unit size 070 for voltages 460/60/3 and575/60/3 (Figure 32) have a five-position terminal blockand are factory wired for high speed. Low speed can beachieved by interchanging black terminal (3) with redterminal (5) and the black and blue terminals (3 & 4)receive a jumper as shown in Figure 33.Figure 32: Size 070 (460/60/3, 575/60/3) factory wired forhigh speed1 (YEL)2 (BRN)3 (BLK)4 (BLU)5 (RED)LINELINEHIGH SPEEDFACTORY WIREDGRNCAPACITORFAN MOTORFigure 33: Size 070 (460/60/3, 575/60/3 low speed1 (YEL)2 (BRN)3 (BLK)4 (BLU)5 (RED)LINELINELOW SPEEDJUMPER LEADGRNCAPACITORFAN MOTORNotes: All motors have a wiring label that is keyed forproper wiring operation. Check unit wiring dia-gram (on electrical access panel) for proper unitoperation. Not all labels are the same.Units leaving the factory are wired for high or lowfan speed (see Table 10 on page 23 for fanspeed settings).Label is located on the back of the terminal block.(Optional) EC MotorThe EC motor will maintain the rated airflow as staticpressure increases or decreases within the unit’soperating range. If an alternate airflow setting is requiredcall 800-432-1342.