5 InstallationInstallation manual8FBA35~140A2VEBSplit system air conditioners4P456962-1C – 2017.04ghjkfifL N1 2 3P1 P2 F1 F2 T1 T2adbcea Switch box coverb Transmission wiring portc Power supply wiring portd Wiring diagrame Switch boxf Plastic clampg User interface wiringh Terminal board for unit transmission wiringi Power supply wiringj Power supply terminal boardk Transmission wiring between units5 Turn ON the power.6 Start cooling operation (see To perform a test run).7 Gradually put approximately 1 l of water through the airdischarge outlet, and check for leaks.cef8dbaa Water inletb Portable pumpc Water inlet coverd Bucket (adding water through water inlet)e Drain outlet for maintenancef Refrigerant pipes8 Turn OFF the power.9 Disconnect the electrical wiring.10 Remove the control box cover.11 Disconnect the power supply and earth.12 Reattach the control box cover.When electrical wiring is finished already1 Start cooling operation (see To perform a test run).2 Gradually pour approximately 1 l of water through the airdischarge outlet, and check for leaks (see When electricalwiring is not finished yet).5.2 Connecting the refrigerant pipingDANGER: RISK OF BURNING5.2.1 To connect the refrigerant piping to theindoor unitWARNING: FLAMMABLE MATERIALThe R32 refrigerant (if applicable) in this unit is mildlyflammable.(a)(a) Refer to the outdoor unit specifications for the type ofrefrigerant to be used.▪ Pipe length. Keep refrigerant piping as short as possible.▪ Flare connections. Connect refrigerant piping to the unit usingflare connections.▪ Insulation. Insulate the refrigerant piping on the indoor unit asfollows:A Ba dc e fb b a dc e fb b243 g 1 23 4gAB1A Gas pipingB Liquid pipinga Insulation material (field supply)b Cable tie (accessory)c Insulation pieces: Large (gas pipe), small (liquid pipe)(accessories)d Flare nut (attached to the unit)e Refrigerant pipe connection (attached to the unit)f Unitg Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe)(accessories)1 Turn up the seams of the insulation pieces.2 Attach to the base of the unit.3 Tighten the cable ties on the insulation pieces.4 Wrap the sealing pad from the base of the unit to the top ofthe flare nut.NOTICEMake sure to insulate all refrigerant piping. Any exposedpiping might cause condensation.5.3 Connecting the electrical wiringDANGER: RISK OF ELECTROCUTIONWARNINGALWAYS use multicore cable for power supply cables.WARNINGIf the supply cord is damaged, it must be replaced by themanufacturer, its service agent or similarly qualifiedpersons in order to avoid a hazard.5.3.1 Guidelines when connecting the electricalwiringTightening torquesWiring Screw size Tightening torque(N•m)Interconnectioncable(indoor↔outdoor)M4 1.18~1.44User interface cable M3.5 0.79~0.97