English 239-4 Computerized control (forced off and on/off operation)(1) Wire specifications and how to perform wiring• Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.(2) Actuation• The following table explains FORCED OFF and ON/OFF OPERATIONS in response to Input A.(3) How to select FORCED OFF and ON/OFF OPERATION• Turn the power on and then use the remote controller to select operation.9-5 Centralized control• For centralized control, it is necessary to designate the group No. For details, refer to the manual of eachoptional controllers for centralized control.10. INSTALLATION OF THE DECORATION PANELRUN” first.>Refer to the installation manual attached to the decoration panel.After installing the decoration panel, ensure that there is no space between the unit body and decoration panel.Note:Since the electric insulation sheet stacked to the control box cover gets sandwiched between the unit body anddecoration panel, when closing the cover, slip the insulation sheet between them first and then attach the coverto the control box.Wire specification Sheathed vinyl cord or cable (2 wire)Gauge AWG18 - 16Length Max. 328ft.External terminal Contact that can ensure the minimum applicable load of 15 V DC, 1 mA.FORCED OFF ON/OFF OPERATIONInput “ON” stops operation (impossible by remote controllers.) Input OFF → ON turns ON unit.Input OFF enables control by remote controller. Input ON → OFF turns OFF unit.F2 T1 T2FORCEDOFFInput A