14Interconnection cable Outdoor unitTerminal BlockIndoor unitTerminal BlockModel Indoor (FDMRN) 36A 50/60AOutdoor (RR) 36A 50/60AVoltage range** Indoor 220-240V/~/50Hz+!Outdoor 380-415V/3N~/50Hz+!Power supply cable size* mm 2Number of conductors2.552.55Interconnection cable size* mm 2Number of conductors2.542.54Recommended time delay fuse* A 16 16COMPLNCOMPLNRSTNAttach insulation sleeveRound crimp-style terminalElectric wireAll wires must be firmly connected.Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.The power supply cord must be equivalent to H07RN-F which is the minimum requirement.Make sure no external pressure is applied to the terminal connectors and wires.Make sure all the covers are properly fixed to avoid any gap.Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matchingto the indication on terminal block. (Refer to the wiring diagram attached on the unit).•••••••Connect wires of thesame gauge to both side.Do not connect wires of thesame gauge to one side.Do not connect wiresof different gauges.Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.Over tightening can damage the terminal screws.Do not connect wire of different gauge to same terminal.Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.••••There must be an all poledisconnection in the supplymains with a contact separationof at least 3mm.!S / L2NMainSwitchFuse /CircuitBreakerPowerSupplyR / L1T / L3PowerSupplyCableFDMRN36/50/60A - RR36/50/60A (3PH)