2 About the documentationInstaller and user reference guide7FFA25~60A2VEB(9)Split system air conditioners4P550955-4 – 2018.08WARNING▪ ONLY use copper wires.▪ Make sure the field wiring complies with the applicablelegislation.▪ All field wiring MUST be performed in accordance withthe wiring diagram supplied with the product.▪ NEVER squeeze bundled cables and make sure theydo NOT come in contact with the piping and sharpedges. Make sure no external pressure is applied to theterminal connections.▪ Make sure to install earth wiring. Do NOT earth the unitto a utility pipe, surge absorber, or telephone earth.Incomplete earth may cause electrical shock.▪ Make sure to use a dedicated power circuit. NEVERuse a power supply shared by another appliance.▪ Make sure to install the required fuses or circuitbreakers.▪ Make sure to install an earth leakage protector. Failureto do so may cause electric shock or fire.▪ When installing the earth leakage protector, make sureit is compatible with the inverter (resistant to highfrequency electric noise) to avoid unnecessary openingof the earth leakage protector.CAUTIONWhen connecting the power supply, the earth connectionmust be made before the current-carrying connections areestablished. When disconnecting the power supply, thecurrent-carrying connections must be separated before theearth connection is. The length of the conductors betweenthe power supply stress relief and the terminal block itselfmust be as such that the current-carrying wires aretautened before the earth wire is in case the power supplyis pulled loose from the stress relief.NOTICEPrecautions when laying power wiring:▪ Do NOT connect wiring of different thicknesses to thepower terminal block (slack in the power wiring maycause abnormal heat).▪ When connecting wiring which is the same thickness,do as shown in the figure above.▪ For wiring, use the designated power wire and connectfirmly, then secure to prevent outside pressure beingexerted on the terminal board.▪ Use an appropriate screwdriver for tightening theterminal screws. A screwdriver with a small head willdamage the head and make proper tighteningimpossible.▪ Over-tightening the terminal screws may break them.WARNING▪ After finishing the electrical work, confirm that eachelectrical component and terminal inside the electricalcomponents box is connected securely.▪ Make sure all covers are closed before starting up theunit.NOTICEOnly applicable if the power supply is three‑phase, and thecompressor has an ON/OFF starting method.If there exists the possibility of reversed phase after amomentary black out and the power goes on and off whilethe product is operating, attach a reversed phaseprotection circuit locally. Running the product in reversedphase can break the compressor and other parts.2 About the documentation2.1 About this documentTarget audienceAuthorised installers + end usersINFORMATIONThis appliance is intended to be used by expert or trainedusers in shops, in light industry, and on farms, or forcommercial and household use by lay persons.Documentation setThis document is part of a documentation set. The complete setconsists of:▪ General safety precautions:▪ Safety instructions that you must read before installing▪ Format: Paper (in the box of the indoor unit)▪ Indoor unit installation and operation manual:▪ Installation and operation instructions▪ Format: Paper (in the box of the indoor unit)▪ Installer and user reference guide:▪ Preparation of the installation, good practices, reference data,…▪ Detailed step-by-step instructions and background informationfor basic and advanced usage▪ Format: Digital files on http://www.daikineurope.com/support-and-manuals/product-information/Latest revisions of the supplied documentation may be available onthe regional Daikin website or via your dealer.The original documentation is written in English. All other languagesare translations.Technical engineering data▪ A subset of the latest technical data is available on the regionalDaikin website (publicly accessible).▪ The full set of latest technical data is available on the Daikinextranet (authentication required).2.2 Installer and user reference guideat a glanceChapter DescriptionGeneral safetyprecautionsSafety instructions that you must readbefore installingAbout the documentation What documentation exists for theinstallerAbout the box How to unpack the units and removetheir accessories