Control Specification SiENBE05-722_A48 Function and Control3.13 Forced Operation ModeOutline Forced operation mode includes only forced cooling.Detail3.14 Standby Electricity SavingRK(X)S25/35G2V1B, RK(X)S25/35G2V1B9 Models OnlyThis function turns power supply OFF to the outdoor unit and sets the indoor unit into energy-saving mode, thus reducing the power consumption of the air conditioner.Field setting is required for turning ON the function.Refer to “Standby Electricity Saving” on page 210 for detail.Item Forced CoolingConditions 1) The outdoor unit is not abnormal and not in the 3-minute standby mode.2) The outdoor unit is not operating.The forced operation is allowed when the above both conditions are met.Start The forced operation starts when any of the following conditions is fulfilled.1) Press the forced operation ON/OFF button (SW1) on the indoor unit for 5seconds.2) Press the forced operation ON/OFF button (SW1) on the outdoor unit.(RK(X)S25/35G2V1B9 models only)Commandfrequency RK(X)S25/35E2V1B, RK(X)S25/35G2V1B: 68 HzRK(X)S25/35G2V1B9: 58 HzEnd The forced operation ends when any of the following conditions is fulfilled.1) The operation ends automatically after 15 minutes.2) Press the forced operation ON/OFF button (SW1) on the indoor unit again.3) Press the ON/OFF button on the remote controlremote control.4) Press the forced operation ON/OFF button (SW1) on the outdoor unit.Others The protection functions are prior to all others in the forced operation.