FMCQ50~125A7VEBAir conditioning system4PW47629-1Installation and operation manual8Summary of field settings■ When using wireless remote controllers it is necessary to useaddress setting. Refer to the installation manual attached to thewireless remote controller for the setting instructions.Control by 2 Remote Controllers (Controlling 1 indoorunit by 2 remote controllers)When using 2 remote controllers, one must be set to "MAIN" and theother to "SUB".Main/sub changeover1. Insert a wedge-head screwdriver into the recess between theupper and lower part of the remote controller and, working fromthe 2 positions, pry off the upper part. (See figure 18)(The remote controller PC board is attached to the upper part ofthe remote controller.)2. Turn the main/sub changeover switch on one of the two remotecontroller PC boards to "S". (See figure 19)(Leave the switch of the other remote controller set to "M".)Computerised control (forced off and on/off operation)1. Wire specifications and how to perform wiring.• Connect input from outside to terminals T1 and T2 of the terminalblock (remote controller to transmission wiring).See figure 17.2. Actuation• The following table explains "forced off" and "on/off operations" inresponse to input A.3. How to select forced off and on/off operation• Turn the power on and then use the remote controller to selectoperation.• Set the remote controller to the field set mode. For details, refer tothe chapter "How to set in the field", in the remote controllermanual.• When in the field set mode, select mode No. 12, then set the firstcode (switch) No. to "1". Then set second code (position) No. to"01" for forced off and to "02" for on/off operation. (forced off atfactory set.) (See figure 16)Centralized controlFor centralized control, it is necessary to designate the group No. Fordetails, refer to the manual of each optional controller for centralizedcontrol.ModeNo.(Note 1)FirstcodeNo. Description of settingSecond code No. (Note 2)01 02 03 0410(20)0Filter contamination- Heavy/Light= Setting to definetime between 2 filtercleaning displayindications. (Whencontamination ishigh, setting can bechanged to half thetime inbetween 2filter cleaningdisplay indications.)Long-lifefilterLight±2,500 hrs.Heavy±1,250 hrs. – –2 Thermostat sensor selectionUse both theunit sensor (orremote sensor ifinstalled) ANDthe remotecontrollersensor.(See note 5+6)Use unit sensoronly (or remotesensor ifinstalled).(See note 5+6)Use remotecontrollersensor only.(See note 5+6)—3Setting for display of timebetween 2 filter cleaning displayindicationsDisplay Do not display — —5 Information to I-manager,I-touch controllerOnly unit sensorvalue (or remotesensor value ifinstalled).Sensor value asset by 10-2-0Xor 10-6-0X.— —6 Thermostat sensor in groupcontrolUse unit sensoronly (or remotesensor ifinstalled).(See note 6)Use both theunit senor (orremote sensor ifinstalled) ANDthe remotecontrollersensor. (Seenote 4+5+6)— —12(22)0 Output signal X1-X2 of theoptional KRP1B PCB kitThermostat-on +compressor run — Operation Mal-function1ON/OFF input from outside(T1/T2 input) = Setting whenforced ON/OFF is to beoperated from outside.Forced OFF ON/OFFoperation — —2Thermostat differentialchangeover = Setting whenremote sensor is used.1°C 0.5°C — —3 Fan setting during thermostatOFF at heating operation LL Set speed OFF(See note 3) —4 Differential automaticchangeover 0°C 1°C 2°C3°C(Seenote 7)5 Auto-restart after power failure Disabled Enabled — —13(23)0Setting for air outletvelocityThis setting is to bechanged in functionof ceiling height.othermodels ≤2.7 m >2.7 ≤3.0 m >3.0 ≤3.5 m —FMCQ125only ≤3.2 m >3.2 ≤3.6 m >3.6 ≤4.2 m —1Selection for air flow directionThis setting is to be changedwhen blocking pad optional kitis used.4-way flow 3-way flow 2-way flow —4Airflow direction range settingThis setting is to be changedwhen range of swing flapmovement needs to bechanged.Upper Medium Lower —Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,indoor units can also be set individually.Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,10-2-02 or 10-2-03 have priority.Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for groupconnection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have priority.Note 7 : More settings for Differential automatic change over temperatures are:Second code No. 05 4°C06 5°C07 6°C08 7°C1 Remote controller PC board2 Factory setting3 Only one remote controller needs to be changedWire specification Sheathed vinyl cord or cable (2 wire)Gauge 0.75-1.25 mm2Length Max. 100 mExternal terminal Contact that can ensure the minimum applicable loadof 15 V DC, 1 mA1 Input AForced off on/off operationInput "on" stops operation input off ➜ on: turns on the unit(impossible by remote controllers)Input "off" enables control input on ➜ off: turns off the unit(by remote controller)1 Second code No.2 Mode No.3 First code No.4 Field set mode