SiBE041029EC Control SpecificationFunction and Control 383.5 Input Current ControlOutline The microcomputer calculates the input current while the compressor is running, and sets thefrequency upper limit based on the input current.In case of heat pump models, this control is the upper limit control of frequency and takespriority over the lower limit control of four way valve operation compensation.DetailFrequency control in each zoneStop zone After 2.5 seconds in this zone, the compressor is stopped.Dropping zone The upper limit of the compressor frequency is defined as operation frequency – 2 Hz. After this, the output frequency is lowered by 2 Hz every second until it reaches the keepzone.Keep zone The present maximum frequency goes on.Reset zone Limit of the frequency is canceled.Limitation of current dropping and stop value according to the outdoor temperature The current drops when outdoor temperature becomes higher than a certain level(depending on the model).RX50G2V1B RX60G2V1BCooling Heating Cooling HeatingA (A) 20.0 20.0B (A) 10.0 15.0 12.0 16.0C (A) 9.0 14.0 11.0 15.0RX50G2V1B9RX50G3V1BRX60G2V1B9RX60G3V1BRX60G4V1B 71 classCooling Heating Cooling Heating Cooling HeatingA (A) 20.0 20.0 20.0B (A) 13.0 15.0 13.0 16.0 17.0 18.75C (A) 12.0 14.0 12.0 15.0 16.0 17.75Compressor StopInput currentDropping ZoneStop ZoneKeep ZoneReset Zone(R14643)A(A)BC