SiBE041011_A TroubleshootingService Diagnosis 974.23 Electrical Box Temperature RiseError Code L3Method of ErrorDetectionAn electrical box temperature rise is detected by checking the radiation fin thermistor with thecompressor off.Error DecisionConditions With the compressor off, the radiation fin temperature is above A°C. The error is cleared when the radiation fin temperature drops below B°C. To cool the electrical components, the outdoor fan starts when the radiation fin temperaturerises above C°C and stops when it drops below B°C.SupposedCauses Defective outdoor fan motor Short circuit Defective radiation fin thermistor Disconnection of connector Defective outdoor unit PCBTroubleshootingCheck No.17Refer to P.108Check No.19Refer to P.109A (°C) B (°C) C (°C)RK(X)S60F3V1B 95 80 85RXS60F4V1B 122 64 11371 class 100 70 85CautionWARNINGTo cool the electrical components,the outdoor fan starts when theradiation fin temperature risesabove C °C and stops when itdrops below B °C.(R14444)YESNOSlightly dirtyNGToo dirtyOKNOYESTurn off the power and turn it onagain.Check the radiation fintemperature.Check No. 17Check the installation condition.Radiation fin dirty?Above A ˚C?Check No. 19Check the outdoor fan orrelated.Error again or outdoorfan activated?Replace the outdoor unitPCB.Clean up the radiation fin.Be sure to turn off the power switch before connecting or disconnectingconnectors, or parts may be damaged.Replace the outdoor fanmotor.Correct the connectorsand fan motor lead wire.Replace the outdoor unitPCB.