• Fan coil • Indoor Unit 5• Indoor Unit • 4-way blow ceiling mounted cassette • FWF-BT2 Specifications12Standard Accessories : Installation and operation manual;Standard Accessories : O ring;Standard Accessories : Insulation;Standard Accessories : Installation guide;Standard Accessories : Screws;Standard Accessories : Washer for hanger bracket;Standard Accessories : Clamp for drain hose;Standard Accessories : Drain hose;Notes(1) Cooling: air 27ºCDB, 19ºCWB; entering water 7ºC; leaving water 12ºC(2) Heating: 2 pipe: air 20ºCDB; entering water 50ºC(3) Do not let water of less than 5ºC or more than 50º/70ºC enter the unit, this may damage the unit(4) Height includes switch box2-1 Technical Specifications FWF02BT FWF03BT FWF04BT FWF05BTCooling capacity Total capacity High kW 2.0 (1) 3.2 (1) 4.2 (1) 5.2 (1)Nom. kW 1.7 (1) 2.8 (1) 3.3 (1) 4.0 (1)Low kW 1.5 (1) 2.5 (1) 2.9 (1)Sensible capacity High kW 1.5 (1) 2.0 (1) 2.8 (1) 3.5 (1)Nom. kW 1.3 (1) 1.7 (1) 2.1 (1) 2.7 (1)Low kW 1.1 (1) 1.4 (1) 1.8 (1)Heating capacity 2-Pipe High kW 2.9 (2) 4.0 (2) 5.4 (2) 6.7 (2)Nom. kW 2.6 (2) 3.4 (2) 4.1 (2) 5.3 (2)Low kW 2.3 (2) 2.8 (2) 3.6 (2)Power input High W 74 90 118Nom. W 67 70 89Low W 60 55 62Casing Material Galvanised steel plateDimensions Unit Height mm 285Width mm 575Depth mm 575Weight Unit kg 19Heat exchanger Rows Quantity 2Fin pitch mm 1.5Water pressure drop Cooling kPa 6 19 31 42Heating kPa 6 19 31 42Fan Type Turbo fanQuantity 1Air flow rate High m³/h 468 660 876Medium m³/h 390 486 648Low m³/h 318 420Fan motor Speed Steps 3Model QTS32C15MSound power level Super high dBA 44 50 55High dBA 42 45 49Low dBA 40 41 42Sound pressure level Super high dBA 31 40 45High dBA 28 34 40Low dBA 26 32Insulation material Foamed polystyrene / foamed polyethylene2-2 Electrical Specifications FWF02BT FWF03BT FWF04BT FWF05BTPower supply Phase 1~Frequency Hz 50Voltage V 220-440